![Siemens QMX3.P02 Скачать руководство пользователя страница 40](http://html.mh-extra.com/html/siemens/qmx3-p02/qmx3-p02_technical-principles_374281040.webp)
40 / 46
Siemens
Wall-mounted sensors and room operator units for KNX/ETS and KNX/ACS
CM2N1602en_05
Building Technologies
ETS engineering
2018-09-14
5.5.11 Operation and display: air quality
Display: Air quality visualization
(
-----
)
Room
X X X
Display: Air quality visualization
Numeric value (ppm)
(
Symbol
)
Text
X X X
Change symbol '+++' <-> '++-' at ppm
400…2000 (1000)
ppm
X X X
Change symbol '++-' <-> '+- -' at ppm
400…2000 (1500)
ppm
X X X
Change text 'Good' <-> 'Okay' at ppm
400…2000 (1000)
ppm
X X X
Change text 'Okay' <-> 'Poor' at ppm
400…2000 (1500)
ppm
X X X
Min. air quality setpoint (ppm)
0…2000 (400)
ppm
X X X
Max. air quality setpoint (ppm)
0…2000 (2000)
ppm
X X X
Air qual. operation in steps of
1;2;5….50;100;200 (100)
ppm
X X X
5.5.12 Operation of light, shading and scenes
Possible function assignment for buttons / button pairs
(8 individual buttons or 4 pairs of buttons).
Only QMX3.P02 and QMX3.P37
Individual buttons
LED response and parameterization
1-button switching/sending value
Edge
Action rising edge [---, Off, On, At, Send percentage value,
Send 8-Bit value]
LED display [object-independent, status
object]
(Action falling edge [---, Off, On, At, Send percentage value,
Send 8-Bit value])
(Object independent) LED constant value
[off, on (orientation light)]
Short button
pressure
Action short button pressure [---, Off, On, At, Send
percentage value, Send 8-Bit value]
( Status object) LED activation [Off/On,
On/Off]
Long button
pressure
Long button pressure via send 2nd object [No, Yes]
Action long button pressure[---, Off, On, At, Send percentage
value, Send 8-Bit value]
1-button dimming
LED display [object-independent,
status object]
Action short/long button pressure [at/dim, On/brighter, Off/darker]
(Object independent) LED constant value
[Off, On (orientation light)]
Long button pressure [0.5 - 6.0s] dimming value 0% or 100%
( status object) LED activation [Off/On,
On/Off]
1-button solar protection / blinds control
No LED display
Action short/long button pressure [stop/up/up, stop/close/down]
Long button pressure [0.5 - 6.0s] move to end positions
Scene
Scene number [1…64]
Selection of predefined scene (short
button pressure <0.5 s). LED On for 3 s
Release scene memory [Yes/Non]
(long button pressure [1 - 6s])
Memorize changed scene (long button
pressure >5 s).
LED flashes for 3 s. When off, user can
release button.