Standards, directives and 
approvals 

Product standard  

EN 60730-1 

Automatic electrical controls for 
household and similar use 

 

Electromagnetic compatibility (Applications)  For use in residential, commerce, light-

industrial and industrial environments 

 

EU conformity (CE) 

CA2T1741xx  *) 

 

UL certification (US) 

UL916,   

http://ul.com/database

 

 

RCM-conformity (EMC) 

A5W00005055   *) 

 

EAC conformity 

Eurasia conformity 

Environmental

 

compatibility  Product environmental declaration (contains 

data on RoHS compliance, materials compo-
sition, packaging, environmental benefit, 
disposal) 

A6V10736277_en--_a  *) 

Dimensions 

See “Dimensions” 

 

Color 

Housing front, dial 

NCS S 0502-G, 

 RAL 9003 signal white 

 

Housing, base unit, rocker switch 

RAL 7035 light grey 

Weight 

Excluding packaging 

0.12 kg 

 
*) The documents can be downloaded from 

http://siemens.com/bt/download

 

Connection  

terminals 

The tool socket on the room unit provides access to the connected individual room 
controller via the commissioning and service tool or the service terminal.  

The bus cable (Terminals 3 and 4) is therefore looped to the tool socket (Pins 1 and 2).  
The bus cable is not affected by the room unit.  

For connection of a service terminal, the PPS2 interface (Terminals 1 and 2) is also 
connected to the tool socket. 
 

8 7

6

5

4

3

2

1

C–

C+

CP

CP

+

80085

 

PPS2 interface, supply voltage 

CP+ 

Device supply, Data PPS2 (pos.) 

CP– 

Device supply, Data PPS2 (neg.)

 

Bus connection (looped to tool socket) 

C+ 

With L

ON

W

ORKS

® bus (Desigo RXC): CLA 

C– 

With L

ON

W

ORKS

® bus (Desigo RXC): CLB 

 

5 ... 8 

Not used

 

 
Standard type RJ45 tool socket. 
 

1

320

6Z

01

2 3 4 5 6 7 8

 

With L

ON

W

ORKS

® bus (Desigo RXC): CLA 

With L

ON

W

ORKS

® bus (Desigo RXC): CLB 

Not used 

Not used 

Not used 

Not used 

CP+  

Data PPS2 

CP– 

Data PPS2 

 
 
 
 
 
 
 
 

Terminal layout 

Tool socket  

Содержание QAX32.1

Страница 1: ...oom unit is used in rooms controlled by an individual room control system to measure the room temperature and for operation of a room controller It can also be used in conjunction with a Desigo PXC automation station 1 The room unit incorporates a socket for a commissioning and service tool or service terminal This tool socket provides access via the PPS2 interface or via a bus system e g LONWORKS...

Страница 2: ...ted circuit board room temperature sensor element setpoint adjuster rocker switch for mode selection plug in connectors and a socket for the commissioning and service tool or service terminal Both the housing and base are made of plastic Base unit Housing 80082 80084 Socket for the commissioning and service tool or service terminal 80167A Dial for stepless adjustment of the setpoint LEDs to indica...

Страница 3: ...om units may be connected to a PXC automation station they are identified by different settings of their address plugs A twisted pair cable is required for the connection to the controller Desigo RX uses four core cables Desigo PX uses two core cables see the respective installation guides Screening is not required Mounting The room unit is suitable for wall mounting and for mounting on a recessed...

Страница 4: ...tion from controller Max 0 10 VA Function data Temperature sensor Measuring element NTC resistor Measuring range 0 40 C Response time 8 min Accuracy 5 30 C 0 5 K Accuracy 25 C 0 25 K Setpoint correction Correction range determined by controller max 12 K default 3 K Accuracy over full correction range 10 Indication control mode 2 LEDs yellow Interfaces Type of interface between controller and room ...

Страница 5: ...ht grey Weight Excluding packaging 0 12 kg The documents can be downloaded from http siemens com bt download Connection terminals The tool socket on the room unit provides access to the connected individual room controller via the commissioning and service tool or the service terminal The bus cable Terminals 3 and 4 is therefore looped to the tool socket Pins 1 and 2 The bus cable is not affected ...

Страница 6: ...ed pair R1 Room unit QAX32 1 N1 Room controller RXC A Connection for RXT10 commissioning and service tool B Connection for service terminal with PPS2 interface Dimensions 9 5 32 36 4 2 60 80087 90 100 56 60 56 Published by Siemens Switzerland Ltd Building Technologies Division International Headquarters Gubelstrasse 22 6301 Zug Switzerland Tel 41 41 724 24 24 www siemens com buildingtechnologies S...