Address plugs inside the housing 

They allow setting the address in cases where several 

room units are connected to one controller. 

The room units are delivered with address 1. 

 

Disposal 

 

The device is classified as waste electronic equipment in terms of the European 
Directive 2012/19/EU (WEEE) and should not be disposed of as unsorted municipal 
waste.  
The relevant national legal rules are to be adhered to.  
Regarding disposal, use the systems setup for collecting electronic waste. 
Observe all local and applicable laws. 
 

Engineering notes 

The device receives its power from the connected controller via the PPS2 interface 
(extra low voltage).

 

Only one room unit may be connected to a RX… room controller.  

A maximum of 5 room units may be connected to a PXC… automation station (they are 
identified by different settings of their address plugs) 

A twisted-pair cable is required for the connection to the controller.  
Desigo RX uses four-core cables, Desigo PX uses two-core cables (see the respective 
installation guides). Screening is not required. 
 

Mounting 

  The room unit is suitable for wall-mounting and for mounting on a recessed conduit 

box.  

  Do not mount in recesses, shelves, behind curtains or doors, or above or near heat 

sources. 

  Avoid exposure to direct sunlight or draughts.  

  The electrical wiring conduit must be sealed where it joins the room unit, to prevent 

the occurrence of draughts in the conduit which could affect the sensor. 

  The specified ambient conditions must be complied with.  

  Mounting instructions are printed on the room unit packaging.  

  A mounting kit is included with the unit. 

 

Installation notes 

Local installation regulations must be observed. 

The room unit is not protected against connection to AC 230 V.  

 

 

 

Address plugs 

STOP

  Note! 

Содержание QAX32.1

Страница 1: ...oom unit is used in rooms controlled by an individual room control system to measure the room temperature and for operation of a room controller It can also be used in conjunction with a Desigo PXC automation station 1 The room unit incorporates a socket for a commissioning and service tool or service terminal This tool socket provides access via the PPS2 interface or via a bus system e g LONWORKS...

Страница 2: ...ted circuit board room temperature sensor element setpoint adjuster rocker switch for mode selection plug in connectors and a socket for the commissioning and service tool or service terminal Both the housing and base are made of plastic Base unit Housing 80082 80084 Socket for the commissioning and service tool or service terminal 80167A Dial for stepless adjustment of the setpoint LEDs to indica...

Страница 3: ...om units may be connected to a PXC automation station they are identified by different settings of their address plugs A twisted pair cable is required for the connection to the controller Desigo RX uses four core cables Desigo PX uses two core cables see the respective installation guides Screening is not required Mounting The room unit is suitable for wall mounting and for mounting on a recessed...

Страница 4: ...tion from controller Max 0 10 VA Function data Temperature sensor Measuring element NTC resistor Measuring range 0 40 C Response time 8 min Accuracy 5 30 C 0 5 K Accuracy 25 C 0 25 K Setpoint correction Correction range determined by controller max 12 K default 3 K Accuracy over full correction range 10 Indication control mode 2 LEDs yellow Interfaces Type of interface between controller and room ...

Страница 5: ...ht grey Weight Excluding packaging 0 12 kg The documents can be downloaded from http siemens com bt download Connection terminals The tool socket on the room unit provides access to the connected individual room controller via the commissioning and service tool or the service terminal The bus cable Terminals 3 and 4 is therefore looped to the tool socket Pins 1 and 2 The bus cable is not affected ...

Страница 6: ...ed pair R1 Room unit QAX32 1 N1 Room controller RXC A Connection for RXT10 commissioning and service tool B Connection for service terminal with PPS2 interface Dimensions 9 5 32 36 4 2 60 80087 90 100 56 60 56 Published by Siemens Switzerland Ltd Building Technologies Division International Headquarters Gubelstrasse 22 6301 Zug Switzerland Tel 41 41 724 24 24 www siemens com buildingtechnologies S...

Отзывы: