QAX30.1, QAX31.1 – Room units with PPS2 interface 

CA2N1741en_02 

Building Technologies 

 

2015-12-23 

Disposal 

 

The device is classified as waste electronic equipment in terms of the European Di-
rective 2012/19/EU (WEEE) and should not be disposed of as unsorted municipal 
waste.  
The relevant national legal rules are to be adhered to.  
Regarding disposal, use the systems setup for collecting electronic waste. 
Observe all local and applicable laws. 
 

Engineering notes 

The device receives its power from the connected controller via the PPS2 interface 
(extra low voltage).

 

Only one room unit may be connected to a RX… room controller.  

A maximum of 5 room units may be connected to a PXC… automation station (they are 
identified by different settings of their address plugs) 

A twisted-pair cable is required for the connection to the controller. Desigo RX uses 
four-core cables, Desigo PX uses two-core cables (see the respective installation 
guides). Screening is not required. 
 

Mounting 

  The room unit is suitable for wall-mounting and for mounting on a recessed conduit 

box.  

  Do not mount in recesses, shelves, behind curtains or doors, or above or near heat 

sources. 

  Avoid exposure to direct sunlight or draughts.  

  The electrical wiring conduit must be sealed where it joins the room unit, to prevent 

the occurrence of draughts in the conduit which could affect the sensor. 

  The specified ambient conditions must be complied with.  

  Mounting instructions are printed on the room unit packaging.  

  A mounting kit is included with the unit. 

 

Installation notes 

Local installation regulations must be observed. 

The room unit is not protected against connection to AC 230 V.  

 

Commissioning notes 

After an interrupt of the PPS2 interface the communication will only be re-established 
when the connected controller polls the PPS2 addresses. The duration of the corre-
sponding cycle is: 
RXA: 10 sec; RXB, RXL and RXC: 3 min; PX: 30 sec. 

 

 

 

 

 

 

STOP

  Note! 

Response on start-up 

Содержание QAX30.1

Страница 1: ...ket for commissioning and service tool or service terminal Use The room units are used in rooms controlled by an individual room control system to measure the room temperature and in the case of the QAX31 1 to adjust the room temperature setpoint They can also be used in conjunction with a Desigo PXC automation station The room units incorporate a socket for a commissioning and service tool or ser...

Страница 2: ...or mounting on a recessed conduit box with the cables connected from the rear The unit comprises a housing and base unit connected by releasable snap fittings The base unit accommodates the screw terminals which have an integrated terminal strip The housing accommodates a printed circuit board room temperature sensor element setpoint adjuster plug in connectors and a socket for the commissioning a...

Страница 3: ... cables Desigo PX uses two core cables see the respective installation guides Screening is not required Mounting The room unit is suitable for wall mounting and for mounting on a recessed conduit box Do not mount in recesses shelves behind curtains or doors or above or near heat sources Avoid exposure to direct sunlight or draughts The electrical wiring conduit must be sealed where it joins the ro...

Страница 4: ...PX CA110396 2 core or 4 core twisted pairs unscreened Connecting cable for service tool Off the shelf max 3 m Protection data Housing protection IP 30 to EN 60529 Protection class III to EN 60730 1 Ambient conditions IEC 721 Operation Transport Ambient air conditions Class 3K5 Class 2K3 Temperature 0 50 C 25 70 C Humidity 85 rH 95 rH Mechanical conditions Class 3M2 Class 2M2 Standards directives a...

Страница 5: ... Device supply Data PPS2 pos CP 2 Device supply Data PPS2 neg Bus connection looped to tool socket C 3 With LONWORKS bus Desigo RXC CLA C 4 With LONWORKS bus Desigo RXC CLB 5 8 Not used Standard type RJ45 tool socket 1 3206Z01 2 3 45 67 8 With LONWORKS bus Desigo RXC CLA With LONWORKS bus Desigo RXC CLB Not used Not used Not used Not used CP Data PPS2 CP Data PPS2 Connection diagram Example RXC Th...

Страница 6: ...5 32 36 4 2 60 80089 90 100 56 60 56 Published by Siemens Switzerland Ltd Building Technologies Division International Headquarters Gubelstrasse 22 6301 Zug Switzerland Tel 41 41 724 24 24 www siemens com buildingtechnologies Siemens Switzerland Ltd 2000 Delivery and technical specifications subject to change ...

Отзывы: