1
Model PAD-5
6
Siemens Industry, Inc.
A6V101030358_en--_c
Smart Infrastructure
Parts Supplied
1. (1) PAD-5 Installation Instructions, Document ID A6V101030358
2. (1) Battery Jumper Wire, P/N A5Q00068677
3. (1) PAD-5 Conn Diagram, P/N A5Q00072441
4. (1) Battery Cable, P/N A5Q00069759
5. (5) Terminal Block Plug
4 POS_0.197”P (5MM) Side Entry Screw Down 30-12 AWG
Green Cable End, P/N 150-150581
6. (4) #10-32 Steel-Zinc Plated Serrated Flange Locknut, McMaster P/N 94831A611 or
Equiv.
7. (4) 24K 1/2W Carbon Film End-Line Resistors, P/N 140-034677
8. (1) Daughter bypass card, P/N A5Q00074788, pre-installed on X901. If using an
expansion module, remove this board from X901 and then install the expansion
module. If not using an expansion module, the bypass card installed on X901,
must not be removed. P2 communication troubles will be present if neither an
expansion card or daughter bypass card are installed on the main board.
1.2 Properties
•
There are four power limited NAC outputs on the PAD-5-MB which have the
following characteristics:
- NAC 1 through NAC 4 (Wiring configuration Class B or Class A).
- Wiring Class configured through the Zeus configuration tool. Each NAC,
whether Class B or A has a maximum output of 3A @ 24VDC.
- For Class A, the naming configuration is NAC 1 and NAC 2. There are only
two outputs on the PAD-5-MB in Class A.
- For Class B wiring, there are 4 NAC circuits (1-4)
- All NACs provide Temporal 3, Temporal 4, March Time 120, 60, 30, 20 and
Steady On bell/horn patterns and synchronization for strobes.
- All NACs can be configured as additional auxiliary outputs through the
software configuration tool.
- All NACs can be configured through Zeus as shorting device inputs, i.e. for
monitoring dry relay contact. Wiring is limited to Class B and these inputs
can be configured as Supervisory, Status or Trouble inputs.
- All NACs are supervised for opens, shorts, and overcurrent.
- Each NAC has independent short circuit and transient protection.
- EOL values of 2.2K through 24K are acceptable and do not need
configuring through the tool.
- Status LEDs for each of the NACs indicate if the specific output is in trouble,
or was previously in trouble, in the case of an intermittent fault.
•
There is one dedicated power limited auxiliary output that has the following
characteristics:
- Auxiliary output is rated a maximum of 3A @ 24VDC
- Supervised for shorts
- Short circuit, overcurrent and transient protection
- Status LED indicates if output is in trouble, or was previously in trouble, in
the case of an intermittent fault Integrated P2 loop circuitry for connection
to Fire Panel device loop (P2) with isolation from short circuit capabilities.