background image

Document No. 129-367 
Installation Instructions  
September 1, 2003 

 

0

self adapt

EA0621R1

 

Figure 12.  Self-adapt Switch in the On Position. 

Factory setting 0 (OFF) 

CAUTION:

 

When turning the self-adaptive feature on, or 
after software reset with the feature on, the 
actuator will enter a five-minute calibration cycle 
as the actuator adjusts to the rotation limits of 
the system. The software reset happens after 
power on, or may be caused by electrostatic 
discharge (ESD) at levels of 2 kV and above. 

 

Slope (span) and Offset adjustment 

For GDE/GLB163x and GDE/GLB164x only 

Factory setting: 
Slope (span) 

10 

Offset Uo = 0 

Use a flat-blade screwdriver to 
make adjustments. The long arm of 
the 

 points to the setting. 

EA0633R2

Uo

U

Ys

V

U

SLOPE,

30

2

16

10

24

Uo

OFFSET,

2

4

0

1

3

5

 

Figure 13. 

 

Wiring 

All wiring must conform to NEC and local codes and 
regulations. 

Use earth ground isolating step-down Class 2 
transformers. Do not use autotransformers. 

Determine the supply transformer rating by summing 
total VA of all actuators used. It is recommended that 
one transformer power no more than 10 actuators. 

 

 

WARNING:  

Installations requiring 

 Conformance 

• 

All wiring for CE rated actuators must only 
be separated extra low voltage (SELV) or 
protective extra low voltage (PELV) per 
HD384-4-41. 

• 

Use safety-isolating transformers (Class 
III transformer) per EN 61558. They must 
be rated for 100% duty cycle. 

• 

Overcurrent protection for supply lines is 
maximum 10A. 

 

Wiring Diagrams 

GDE/GLB13x 

Counterclockwise Damper Rotation of GDE/GLB13x 

If the damper blades turn counterclockwise to open (CCW), 
reverse the 6 (violet) and 7 (orange) wires at the controller.

 

CAUTION:  

Do not wire different types of actuators (such as 
GBB or GIB actuators) in parallel with these 
models. 

 

Page 4 of 6 

Siemens Building Technologies, Inc.  

Содержание OpenAir GDE131.1P

Страница 1: ...you do not follow a procedure as specified CAUTION Equipment damage or loss of data may occur if you do not follow a procedure as specified Instructions WARNING Do not open the actuator NOTE Place the actuator on the damper shaft so that the front of the actuator is accessible The label is on the front side 1 Determine whether the damper blades will rotate clockwise or counterclockwise to open See...

Страница 2: ...nstalled 1 2 inch guide See Figure 3 EA0999R1 Figure 3 Removing 1 2 inch Ø shaft guide for 3 8 in or 5 8 in shaft 45 90 90 EA0679R3 f Mounting GDE GLB on 3 8 inch 8 10 mm shafts Figure 4 3 8 Ø inch shaft see Figure 1 Item f 1 A 3 8 inch shaft adapter is provided in actuator package 2 Hold the shaft insert so that the raised tabs are inserted last when placing the insert into the back of the actuat...

Страница 3: ... of the points to the setting Manually turn the red ring of the B switch The narrower tab on the ring points to the setting See Figure 10 The auxiliary switch setting shafts rotate with the actuator NOTE The scale is valid only when the actuator is in the 0 position on clockwise motion 80 70 60 20 10 AUX SWITCH ADJUSTMENT A B 50 EA0636R2 Figure 10 Auxiliary Switch Setting Dial Mechanical Range Adj...

Страница 4: ...iring must conform to NEC and local codes and regulations Use earth ground isolating step down Class 2 transformers Do not use autotransformers Determine the supply transformer rating by summing total VA of all actuators used It is recommended that one transformer power no more than 10 actuators WARNING Installations requiring Conformance All wiring for CE rated actuators must only be separated ex...

Страница 5: ...position control Each wire has the standard symbol printed on it See Table 1 M A B 1000 P1 P3 P2 S1 S4 S2 S3 S5 S6 1 6 7 EA0282R1 EA0635R2 24 Vac EARTH GROUND ISOLATING CLASS 2 TRANSFORMER FOR 24 Vac POWER SAFETY ISOLATING TRANSFORMER PER EN 60742 120 Vac 7 ORANGE 6 VIOLET 1 RED NEUT Figure 14 3 position Control GDE GLB16x 24 Vac power supply 0 to 10V modulating control Each wire has the standard ...

Страница 6: ...88P25 OpenAir Electronic Damper Actuators GDE GLB Series Non spring Return Rotary 24 Vac Three Position Control Information in this publication is based on current specifications The company reserves the right to make changes in specifications and models as design improvements are introduced OpenAir is a trademark of Siemens Building Technologies Inc Other product or company names mentioned herein...