Technical Instructions
OpenAir™ GCA Series Spring Return 160 lb-in Electronic Damper Actuator
Document No. 155-173P25
May 19, 2014
Page 4
Siemens Industry, Inc.
Specifications,
Continued
Mounting
Nominal angle of rotation
90°
Maximum angular rotation
95°
Shaft size
3/8-inch to 1-inch
(8 mm to 25.6 mm) diameter
1/4-inch to 5/8-inch
(6 to 18 mm) square
Minimum shaft length
3/4-inch (20 mm)
Auxiliary features
Control signal adjustment
Offset (start point)
0 Vdc to 5 Vdc
Factory setting
0 Vdc
Span
2 Vdc to 30 Vdc
Dual auxiliary switches
AC rating (Standard cable)
24 Vac to 250 Vac
AC 6A resistive
AC 2A FLA, 12 LRA
AC rating (Plenum cable)
24 Vac
AC 4A resistive
AC 2A, FLA, 12 LRA
DC rating (Standard/Plenum cable)
12 Vdc to 30 Vdc
DC 2A
Switch Range
Switch A
0 to 90° with 5° intervals
Recommended range usage
0 to 45°
Factory setting
5°
Switch B
0 to 90° with 5° intervals
Recommended range usage
45° to 90°
Factory setting
85°
Switching hysteresis
2°
WARNING:
Apply only AC-line voltage from the same phase or only UL-Class 2 voltage to
the switching outputs of both auxiliary switches A and B. Mixed operation is not
permissible.
NOTE:
With plenum cables, only UL-Class 2 voltage is permitted.
Housing
Enclosure
NEMA 2,
IP54 per EN 60 529
in vertical to horizontal 90°
See Figure 17.
NEMA 3R rated when installed with
ASK75.1U Weather Shield in the
vertical position. See Figure 18.
See
Accessories,
Figure 9
.
Material
Die-cast aluminum alloy
Gear lubrication
Silicone-free