Technical Instructions
OpenAir™ GCA Series Spring Return 160 lb-in Electronic Damper Actuator
Document No. 155-173P25
May 19, 2014
Page 18
Siemens Industry, Inc.
Table 4. Wire Designations.
Standard
Symbol
Function
Terminal
Designations
Color
Standard
Plenum
1
Supply (SP)
G
Red
Red
2
Neutral (SN)
G0
Black
Black
3
Line (120 Vac)
L
Black
Black
4
Neutral (120 Vac)
N
White
White
6
Control Signal clockwise (GCA13x)
Y1
Violet
Violet
7
Control Signal counterclockwise (GCA13x)
Y2
Orange
Orange
8
Input signal: 0 to 10 Vdc (GCA16x) or 2 to 10 Vdc (GCA15x)
Y
Gray
Gray
9
Position output: 0 to 10 Vdc (GCA15x & GCA16x)
U
Pink
Pink
S1
Switch A Common
Q11
Gray/red
Gray/red
S2
Switch A NC
Q12
Gray/blue
Gray/blue
S3
Switch A NO
Q14
Gray/pink
Gray/pink
S4
Switch B Common
Q21
Black/red
Black/red
S5
Switch B NC
Q22
Black/blue
Black/blue
S6
Switch B NO
Q24
Black/pink
Black/pink
P1
Feedback Potentiometer 0 to 100% P1 – P2
A
White/red
Black
P2
Feedback Potentiometer – Common
B
White/blue
Black
P3
Feedback Potentiometer 100 to 0% P3 – P2
C
White/pink
Black
Start-Up/
Commissioning
GCA12x
(24 Vac/dc)
GCA22x (120 Vac)
1. Check Operation:
a. Switch on Vac/dc power.
b. Allow the actuator shaft coupling to rotate from 0 to 90°.
c. Switch off Vac/dc power.
The actuator shaft coupling will return to the "0" position.
2. Check Spring Return:
a. Switch on Vac power.
b. Allow the actuator shaft coupling to rotate halfway.
c. Switch off Vac power.
The spring returns the actuator shaft coupling to the fail "0" position.
3. Check the Auxiliary Switch A:
a. Set the DMM dial to ohms (resistance) or continuity check.
b. Connect wires S1 and S3 to the DMM.
The DMM should indicate an open circuit or no resistance.
c. Switch on Vac power.
The DMM should indicate contact closure as the actuator shaft coupling
reaches the setting of switch A.
d. Connect wires S1 and S2 to the DMM.
The DMM should indicate open circuit or no resistance.
e. Switch off Vac power.
The DMM should indicate contact closure as the actuator shaft coupling
reaches the setting of switch A.