Operation, Continued

CAUTION:

Before resetting any sensor, carefully
inspect the damper, damper actuator, and
sensor. Verify whether or not local
authorities or building managers must be
contacted.

Damage to the temperature sensor will
result in loss of damper control.

WARNING:

Before attempting to reset the EFL by
pressing the Override/reset button, take
the precaution to protect exposed skin as
the EFL will be extremely hot to the touch.

Installation

Figure 2.  The EFL and OpenAir Fire and Smoke Damper

Actuator.

WARNING:

The internal/external mounting orientation
or position in the duct will affect the time
and/or temperature the EFL requires to
switch.

NOTE:

  Notice the position of the top clip before

attempting to couple the actuator with the EFL
sensor.

Figure 3.  Proper Clip Positioning.

Internal Mounting

For internal mounting, the reset button must protrude
through a 3/8-inch (9.5 mm) diameter relief hole
providing operator access for resetting the EFL.

CAUTION:

Failure to provide a relief hole will keep
the reset button pressed against the duct
wall or damper sleeve, and the EFL will
fail to operate as intended.

Содержание OpenAir ASK791.165

Страница 1: ...t Numbers ASK791 165 165 F 74 C ASK791 212 212 F 100 C ASK791 250 250 F 121 C ASK791 350 350 F 177 C NOTE The EFL is compatible only with OpenAir GJD GRD GKD or GVD fire and smoke damper actuators Warning Caution Notations WARNING Personal injury or loss of life may occur if you do not follow the procedures as specified CAUTION Equipment damage may occur if you do not follow the procedures as spec...

Страница 2: ...extremely hot to the touch Installation Figure 2 The EFL and OpenAir Fire and Smoke Damper Actuator WARNING The internal external mounting orientation or position in the duct will affect the time and or temperature the EFL requires to switch NOTE Notice the position of the top clip before attempting to couple the actuator with the EFL sensor Figure 3 Proper Clip Positioning Internal Mounting For i...

Страница 3: ...ecified mounting screw torque may damage the housings External Mounting For external mounting make a 1 3 8 inch 35 mm diameter hole in the duct wall or damper sleeve The sensor will protrude into the duct or damper for proper temperature sensing Figure 5 Providing Proper Sensor Temperature Detection Access CAUTION Exceeding the specified mounting screw torque may damage the housings ...

Страница 4: ...chweiz AG Other product or company names mentioned herein may be the trademarks of their respective owners 2018 Siemens Industry Inc Siemens Industry Inc Building Technologies Division 1000 Deerfield Parkway Buffalo Grove IL 60089 1 847 215 1000 Your feedback is important to us If you have comments about this document please send them to sbt_technical editor us sbt siemens com Document No A6V11200...

Отзывы: