Siemens NRC Скачать руководство пользователя страница 3

Siemens Industry, Inc.
Building Technologies  Division

3

A6V10322639_b_en_--

FIRMWARE UPGRADES

From time to time, modules used in XLS systems are upgraded to improve their
operation or to add to their capabilities with new features. Firmware in the NRC is
field upgradable. Refer to the Zeus Quickstart Manual, P/N 315-033875, and Zeus
Help for additional details.

Find NRC Software Version

To check for the current version of NRC software in an installed NRC, go to the PMI/
PMI-2 and press the Menu button, select Report, press the More Info button and
select the PMI. Press the Configuration soft key and “Touch” Appl Rev for the
Application Version. The NRC software version will be shown with the PMI software
version. Refer to Figure 3 for an example of a display.

Figure 3

Typical PMI Display of NRC Software Version

Menu:Report:Configuration:Appl.Rev:View
PHY:MultiXNet, FireFinder, PMI-C@253

Application Rev Report

Cancel

Print

10:53

Category text information

Address

Entity

Software Version

100%

/1:253

PMI-C

07.00.0034

/1:253^1

NRC

01.00.0008

GoTo

Содержание NRC

Страница 1: ... this configuration all events occurring on the FireFinder XLS network are displayed at the NCCNT G One NRC is required in each FireFinder XLS system on the network This NRC must reside in the same enclosure as the PMI PMI 2 The NRC supervises the network to ensure proper opera tion Any faults that are detected by the NRC are reported to the PMI PMI 2 for annunciation In addition the NRC has diagn...

Страница 2: ...failure The Trouble LED will illuminate under the following conditions 1 Wire faults open or short in either Port 1 In or Port 2 Out See Figure 5 2 Ground fault on outgoing port Port 2 3 XNET communications problems between the PMI PMI 2 and the NRC PRE INSTALLATION The NRC does not have a network address but it does need to be included in the Zeus configuration INSTALLATION The NRC plugs perpendi...

Страница 3: ... NRC software in an installed NRC go to the PMI PMI 2 and press the Menu button select Report press the More Info button and select the PMI Press the Configuration soft key and Touch Appl Rev for the Application Version The NRC software version will be shown with the PMI software version Refer to Figure 3 for an example of a display Figure 3 Typical PMI Display of NRC Software Version Menu Report ...

Страница 4: ...4 15 16 17 18 19 20 21 22 23 24 DO NOT USE ONE SLOT OF CC 5 LAST NRC DO NOT USE DO NOT USE DO NOT USE DO NOT USE DO NOT USE Figure 5 NRC Network Wiring Style 7 Figure 4 NRC Wiring 1 5 2 6 3 7 4 8 TOP HEADER OF TERMINAL BLOCK ON THE CC 5 CC 2 PORT 1 PORT 2 A1 B1 A2 B2 B2 A2 B1 A1 NOTES 1 No EOLR required 2 22 AWG min 12 AWG max 3 3300 feet max per pair between NRCs Shielded or Unshielded twisted pa...

Страница 5: ...Power limited to NFPA 70 6 All wires supervised 7 Ground fault detected at 8 5K ohms or less Figure 6 NRC Class B Style 4 Network Wiring Power B connections to the fiber module and monitoring of its trouble contacts are not required as the fiber modules must be installed in the same enclosure as the power supplies that provide them power NRC with NCC See the NCC WAN IOM manual P N 315 049679 for i...

Страница 6: ...R PAIR FOM FN2006 FN2007 PORT 2 PORT 1 PORT 2 PORT 1 PORT 2 PORT 1 WIRE CONNECTION WIRE CONNECTION WIRE CONNECTION WIRE CONNECTION NRC In Node 1 NRC In Node 2 NRC In Node n FOM FN2006 FN2007 OPTICAL FIBER PAIR OPTICAL FIBER PAIR FOM FN2006 FN2007 OPTICAL FIBER PAIR WIRE CONNECTION WIRE CONNECTION FOM FN2006 FN2007 PORT 2 PORT 1 PORT 2 PORT 1 PORT 2 PORT 1 WIRE CONNECTION WIRE CONNECTION WIRE CONNE...

Страница 7: ... FOM FN2006 FN2007 OPTICAL FIBER PAIR FOM FN2006 FN2007 OPTICAL FIBER PAIR WIRE CONNECTION WIRE CONNECTION WIRE CONNECTION FOM FN2006 FN2007 WIRE CONNECTION WIRE CONNECTION PORT 2 PORT 1 PORT 2 PORT 1 PORT 2 PORT 1 r e w o P t u p n I t n e r r u C e n a l P k c a B V 4 2 A m 0 4 1 t n e r r u C V 4 2 l a n i m r e T w e r c S 0 t n e r r u C e n a l P k c a B V 2 6 A m 0 2 t n e r r u C y b d n a...

Страница 8: ...echnologies Division Florham Park NJ Siemens Canada Limited Building Technologies Division 2 Kenview Boulevard Brampton Ontario L6T 5E4 Canada Document ID A6V10322639_b_en_ P N A5Q00059298 This page has been left intentionally blank ...