Figure 2

Installing the NRC

OPERATION

The NRC continuously monitors the network for activity and reports any problems to
the PMI/PMI-2. In some cases, a reset at the PMI/PMI-2 is required to clear network
troubles.

Controls and Indicators

The front panel of the NRC contains one reset switch, three
LEDs, one Monitor port, one USB port, and one Ethernet port as shown in
Figure 1.

A reset switch is located on the top of the front panel. Pushing the reset switch
reinitializes the NRC.

The LEDs follow the reset switch and their functions are defined as follows:

POWER

(Green)

Normally ON. When illuminated, indi-
cates that power for the NRC is applied
to the card.

CARD FAIL

(Yellow)

Normally OFF. When illuminated, indicates
that the card microprocessor has failed.

TROUBLE

(Yellow)

Normally OFF. When illuminated, indi-
cates trouble in the Network such as
wire faults or module failure. The Trouble
LED will illuminate under the following
conditions:
1.   Wire faults (open or short) in either
Port 1 (In) or Port 2 (Out)—See Figure 5.
2.  Ground fault on outgoing port (Port 2).
3.  XNET communications problems
between the PMI/PMI-2 and the NRC.

PRE-INSTALLATION

The NRC does not have a network address but it does need to be included in the
Zeus configuration.

INSTALLATION

The NRC plugs perpendicularly into one slot in the CC-2 or CC-5 card-cage via two
96-pin DIN connectors (only 64-pins are used) and can occupy any slot in the card
cage. (Refer to Figure 2.)

Slide the NRC card into the card guides front bezel up (lettering on the
front panel is legible) until the card cage connectors contact the
motherboard receptacles.

Verify that the card edge connectors align properly with the
motherboard receptacles. There is only one correct way to plug in the
card. If it does not align, DO NOT FORCE the card.

Place thumbs on the front panel adjacent to the captive screws and
gently apply even pressure on the card until the connectors plug firmly
into the motherboard receptacles. Secure the NRC to the card cage with
the captive screws.

Содержание NRC

Страница 1: ... this configuration all events occurring on the FireFinder XLS network are displayed at the NCCNT G One NRC is required in each FireFinder XLS system on the network This NRC must reside in the same enclosure as the PMI PMI 2 The NRC supervises the network to ensure proper opera tion Any faults that are detected by the NRC are reported to the PMI PMI 2 for annunciation In addition the NRC has diagn...

Страница 2: ...failure The Trouble LED will illuminate under the following conditions 1 Wire faults open or short in either Port 1 In or Port 2 Out See Figure 5 2 Ground fault on outgoing port Port 2 3 XNET communications problems between the PMI PMI 2 and the NRC PRE INSTALLATION The NRC does not have a network address but it does need to be included in the Zeus configuration INSTALLATION The NRC plugs perpendi...

Страница 3: ... NRC software in an installed NRC go to the PMI PMI 2 and press the Menu button select Report press the More Info button and select the PMI Press the Configuration soft key and Touch Appl Rev for the Application Version The NRC software version will be shown with the PMI software version Refer to Figure 3 for an example of a display Figure 3 Typical PMI Display of NRC Software Version Menu Report ...

Страница 4: ...4 15 16 17 18 19 20 21 22 23 24 DO NOT USE ONE SLOT OF CC 5 LAST NRC DO NOT USE DO NOT USE DO NOT USE DO NOT USE DO NOT USE Figure 5 NRC Network Wiring Style 7 Figure 4 NRC Wiring 1 5 2 6 3 7 4 8 TOP HEADER OF TERMINAL BLOCK ON THE CC 5 CC 2 PORT 1 PORT 2 A1 B1 A2 B2 B2 A2 B1 A1 NOTES 1 No EOLR required 2 22 AWG min 12 AWG max 3 3300 feet max per pair between NRCs Shielded or Unshielded twisted pa...

Страница 5: ...Power limited to NFPA 70 6 All wires supervised 7 Ground fault detected at 8 5K ohms or less Figure 6 NRC Class B Style 4 Network Wiring Power B connections to the fiber module and monitoring of its trouble contacts are not required as the fiber modules must be installed in the same enclosure as the power supplies that provide them power NRC with NCC See the NCC WAN IOM manual P N 315 049679 for i...

Страница 6: ...R PAIR FOM FN2006 FN2007 PORT 2 PORT 1 PORT 2 PORT 1 PORT 2 PORT 1 WIRE CONNECTION WIRE CONNECTION WIRE CONNECTION WIRE CONNECTION NRC In Node 1 NRC In Node 2 NRC In Node n FOM FN2006 FN2007 OPTICAL FIBER PAIR OPTICAL FIBER PAIR FOM FN2006 FN2007 OPTICAL FIBER PAIR WIRE CONNECTION WIRE CONNECTION FOM FN2006 FN2007 PORT 2 PORT 1 PORT 2 PORT 1 PORT 2 PORT 1 WIRE CONNECTION WIRE CONNECTION WIRE CONNE...

Страница 7: ... FOM FN2006 FN2007 OPTICAL FIBER PAIR FOM FN2006 FN2007 OPTICAL FIBER PAIR WIRE CONNECTION WIRE CONNECTION WIRE CONNECTION FOM FN2006 FN2007 WIRE CONNECTION WIRE CONNECTION PORT 2 PORT 1 PORT 2 PORT 1 PORT 2 PORT 1 r e w o P t u p n I t n e r r u C e n a l P k c a B V 4 2 A m 0 4 1 t n e r r u C V 4 2 l a n i m r e T w e r c S 0 t n e r r u C e n a l P k c a B V 2 6 A m 0 2 t n e r r u C y b d n a...

Страница 8: ...echnologies Division Florham Park NJ Siemens Canada Limited Building Technologies Division 2 Kenview Boulevard Brampton Ontario L6T 5E4 Canada Document ID A6V10322639_b_en_ P N A5Q00059298 This page has been left intentionally blank ...

Отзывы: