background image

Siemens Industry, Inc.
Building Technologies  Division

4

A6V10322639_b_en_--

WIRING

Remove all system power before installation, first battery then AC. (To power up,
connect the AC first, then the battery.)

All field wiring to the NRC is connected to the terminal blocks of the CC-2 or CC-5
card cage slot in which it is installed.

To connect the field wiring:

1.

Loosen the screw of the terminal by turning it counterclockwise.

2.

Insert the wire into the side of the terminal block.

3.

Tighten the screw of the terminal block by turning it clockwise.

The screw terminals can accommodate one 12 - 22 AWG.

     

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

DO NOT USE

ONE SLOT OF CC-5

FIRST NRC

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

DO NOT USE

DO NOT USE

ONE SLOT OF CC-5

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

DO NOT USE

ONE SLOT OF CC-5

LAST NRC

DO NOT USE

DO NOT USE

DO NOT USE

DO NOT USE

DO NOT USE

Figure 5

NRC Network Wiring Style 7

Figure 4

NRC Wiring

1

5

2

6

3

7

4

8

TOP HEADER OF

TERMINAL BLOCK

ON THE CC-5/CC-2

PORT 1

PORT 2

A1
B1

A2
B2

B2

A2

B1

A1

NOTES:
1. No EOLR required.
2. 22 AWG min., 12 AWG max.
3. 3300 feet max. per pair

between NRCs.
Shielded or Unshielded
twisted pair with a minimum
of 3 twists per ft.
Refer to Table 1 for NRC
cable specifications.

4. Terminate shields at one end

only.

5. Power limited to NFPA 70.
6. All wires supervised.
7. Ground fault detected at

8.5K ohms or less.

1

E

L

B

A

T

s

n

o

i

t

a

c

i

f

i

c

e

p

S

e

l

b

a

C

C

R

N

.

e

l

b

a

c

e

h

t

n

o

t

n

e

m

e

r

i

u

q

e

r

m

u

m

i

n

i

m

e

h

t

s

w

o

h

s

w

o

l

e

b

e

l

b

a

t

e

h

T

z

H

K

0

0

1

t

a

n

o

i

t

a

u

n

e

t

t

A

x

a

m

B

d

0

1

z

H

M

1

t

a

n

o

i

t

a

u

n

e

t

t

A

x

a

m

B

d

0

3

:

s

t

n

e

m

e

r

i

u

q

e

r

e

s

e

h

t

t

e

e

m

s

e

p

y

t

e

l

b

a

c

g

n

i

w

o

ll

o

f

e

h

T

E

5

-

T

A

C

A

2

2

9

7

n

e

d

l

e

B

G

W

A

8

1

L

U

0

2

3

5

n

e

d

l

e

B

Содержание NRC

Страница 1: ... this configuration all events occurring on the FireFinder XLS network are displayed at the NCCNT G One NRC is required in each FireFinder XLS system on the network This NRC must reside in the same enclosure as the PMI PMI 2 The NRC supervises the network to ensure proper opera tion Any faults that are detected by the NRC are reported to the PMI PMI 2 for annunciation In addition the NRC has diagn...

Страница 2: ...failure The Trouble LED will illuminate under the following conditions 1 Wire faults open or short in either Port 1 In or Port 2 Out See Figure 5 2 Ground fault on outgoing port Port 2 3 XNET communications problems between the PMI PMI 2 and the NRC PRE INSTALLATION The NRC does not have a network address but it does need to be included in the Zeus configuration INSTALLATION The NRC plugs perpendi...

Страница 3: ... NRC software in an installed NRC go to the PMI PMI 2 and press the Menu button select Report press the More Info button and select the PMI Press the Configuration soft key and Touch Appl Rev for the Application Version The NRC software version will be shown with the PMI software version Refer to Figure 3 for an example of a display Figure 3 Typical PMI Display of NRC Software Version Menu Report ...

Страница 4: ...4 15 16 17 18 19 20 21 22 23 24 DO NOT USE ONE SLOT OF CC 5 LAST NRC DO NOT USE DO NOT USE DO NOT USE DO NOT USE DO NOT USE Figure 5 NRC Network Wiring Style 7 Figure 4 NRC Wiring 1 5 2 6 3 7 4 8 TOP HEADER OF TERMINAL BLOCK ON THE CC 5 CC 2 PORT 1 PORT 2 A1 B1 A2 B2 B2 A2 B1 A1 NOTES 1 No EOLR required 2 22 AWG min 12 AWG max 3 3300 feet max per pair between NRCs Shielded or Unshielded twisted pa...

Страница 5: ...Power limited to NFPA 70 6 All wires supervised 7 Ground fault detected at 8 5K ohms or less Figure 6 NRC Class B Style 4 Network Wiring Power B connections to the fiber module and monitoring of its trouble contacts are not required as the fiber modules must be installed in the same enclosure as the power supplies that provide them power NRC with NCC See the NCC WAN IOM manual P N 315 049679 for i...

Страница 6: ...R PAIR FOM FN2006 FN2007 PORT 2 PORT 1 PORT 2 PORT 1 PORT 2 PORT 1 WIRE CONNECTION WIRE CONNECTION WIRE CONNECTION WIRE CONNECTION NRC In Node 1 NRC In Node 2 NRC In Node n FOM FN2006 FN2007 OPTICAL FIBER PAIR OPTICAL FIBER PAIR FOM FN2006 FN2007 OPTICAL FIBER PAIR WIRE CONNECTION WIRE CONNECTION FOM FN2006 FN2007 PORT 2 PORT 1 PORT 2 PORT 1 PORT 2 PORT 1 WIRE CONNECTION WIRE CONNECTION WIRE CONNE...

Страница 7: ... FOM FN2006 FN2007 OPTICAL FIBER PAIR FOM FN2006 FN2007 OPTICAL FIBER PAIR WIRE CONNECTION WIRE CONNECTION WIRE CONNECTION FOM FN2006 FN2007 WIRE CONNECTION WIRE CONNECTION PORT 2 PORT 1 PORT 2 PORT 1 PORT 2 PORT 1 r e w o P t u p n I t n e r r u C e n a l P k c a B V 4 2 A m 0 4 1 t n e r r u C V 4 2 l a n i m r e T w e r c S 0 t n e r r u C e n a l P k c a B V 2 6 A m 0 2 t n e r r u C y b d n a...

Страница 8: ...echnologies Division Florham Park NJ Siemens Canada Limited Building Technologies Division 2 Kenview Boulevard Brampton Ontario L6T 5E4 Canada Document ID A6V10322639_b_en_ P N A5Q00059298 This page has been left intentionally blank ...

Отзывы: