Shields

Shields for the XNET must be connected at ONE
and ONLY ONE end of the network. If you wish
to terminate the shields at the NCC-G computer,
use terminal 5 on the NCC-1F. See Figure 2.

Earth Ground

A good earth ground must be provided for proper
transient protection of the NCC-1F and the
NCC-G computer. Connect a separate ground to
terminal 6 on the NCC-1F (Refer to Figure 2).

Ground Fault Detection

The NCC-1F provides electrical isolation be-
tween the NCC-G computer and the XNET. This
allows for ground fault detection to be enabled on
the XNET. Ground fault detection is only possible
if ALL NCC-G computers in the system are
connected to XNET with an NCC-1F.

Ground fault detection must be enabled at a
NIM-1R/-1W or NIC-C. Select one and only one
NIM-1R/-1W or NIC-C in the system where the
ground fault is to be detected. You must locate
the NIM-1R/-1W in a cabinet with either an MMB,
SMB or a PSR-1. See Figure 3 for the wiring
diagram.

If the XNET is divided into multiple sections of
copper wire using fiber optic segments, ground
fault detection can be enabled at one NIM-1R/-1W
or NIC-C for each section of copper wire. Refer to
the NIC-C Installation Instructions, P/N 315-
033240 if you wish to use the NIC-C to provide
ground fault detection.

ELECTRICAL RATINGS

NCC-1F:

5 VDC @ 250mA

Network (XNET):

8V P-P, 190mA max

TB3

NIM-1R/-1W

IN TB4

NIM-1R/-1W

IN TB3

USE ONLY ONE

TB5

TB4

MOM-2

MOM-4

TB7

TB4

13

14

15

16

9

10

11

12

13

14

15

16

12

13

14

15

16

12

5

6

7

8

+

1

1

2

2

3

4

_

+

1

2

_

Figure 3

Wiring for Ground Fault Detection

Содержание NCC-1F

Страница 1: ...ses this does not need to be changed If COM 2 is not available Installation Instructions Model NCC 1F NCC G XNET Interface use Table 1 to select the desired COM port Be sure to configure the NCC G computer to use the same port and IRQ for XNET communications See Figure 1 for the location of the jumpers Figure 1 NCC 1F Module Board TABLE 1 CONFIGURING THE NCC 1F COM JP1 JP2 ADDRESS JP3 IRQ 1 A C 3F...

Страница 2: ...T The XNET connections are made on terminals 1 4 of the terminal block on the rear of the NCC 1F The primary pair or network A is on terminals 1 and 2 The secondary pair or network B is on terminals 3 and 4 For Style 4 networks install a 120 ohm EOLR on terminals 3 and 4 See Figure 2 for wiring details For Style 7 networks connect to both the primary and secondary pairs See Figure 2 for wiring det...

Страница 3: ...NCC 1F Ground fault detection must be enabled at a NIM 1R 1W or NIC C Select one and only one NIM 1R 1W or NIC C in the system where the ground fault is to be detected You must locate the NIM 1R 1W in a cabinet with either an MMB SMB or a PSR 1 See Figure 3 for the wiring diagram If the XNET is divided into multiple sections of copper wire using fiber optic segments ground fault detection can be e...

Страница 4: ...P N 315 095965 8 Siemens Industry Inc Building Technologies Division Florham Park NJ Siemens Building Technologies Ltd Fire Safety Security Products 2 Kenview Boulevard Brampton Ontario L6T 5E4 Canada ...

Отзывы: