The NCC-1F also provides IRQs 5, 7, 9, 10, 11,
12, 14, and 15. These can be used in conjunction
with COM 3 and COM 4 if IRQs 3 and 4 are used
by other hardware. When using these IRQs be
sure that no other hardware has been assigned
to the IRQ used on the NCC-1F.

INSTALLATION

Remove all NCC-G power before installation.

To install the NCC-1F follow the steps listed below:

1. Unscrew the two knurled knobs on the rear of

the NCC-G computer.

2. Slide the cover back an inch or so and lift it off.

3. The NCC-1F installs into any free 16-Bit

ISA slot in the NCC-G computer. Select a slot
and remove the blank cover, keeping
the screw.

4. Remove the terminal block from the NCC-1F

by removing the two screws that hold it to the
bracket.

5. Place the NCC-1F into the open slot so that

the NCC-1F card edge extends through the
opening in the back of the PC.

6. Align the NCC-1F with the card edge

connector in the NCC-G computer and
press it firmly into place.

7. Secure the NCC-1F by installing the screw

that held the blank cover. (Refer to Step 3.)

8. Replace the NCC-G computer cover and

tighten the knurled knobs.

9. Reattach the terminal block by sliding it

onto the NCC-1F card edge and install the
two screws. This is a keyed connection
and will only install one way.

ELECTRICAL CONNECTIONS

Network (XNET)

The XNET connections are made on terminals
1-4 of the terminal block on the rear of the
NCC-1F. The primary pair (or network A) is
on terminals 1 and 2. The secondary pair (or
network B) is on terminals 3 and 4.

For Style 4

 

networks,

 install a 120 ohm EOLR

on terminals 3 and 4. See Figure 2 for wiring
details.

For Style 7 networks,

 connect to both the

primary and secondary pairs. See Figure 2 for
wiring details.

Figure 2

NCC-1F XNET Connections

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

SEE NOTE 7

DO NOT USE

DO NOT USE

DO NOT USE

DO NOT USE

ONE SLOT OF CC-5

NIC-C

1

2

3

4

5

6

PAIR A

SUPERVISED

POWER LIMITED

PAIR B

(OMIT FOR STYLE 4)

SUPERVISED

POWER LIMITED

LOCATED INSIDE NCC

NOTE:

IF THE NCC IS LOCATED

AT THE END OF THE XNET

NETWORK, INSTALL EOLR

P/N 140-820350 ACROSS

TERMINALS 1 & 2 AND 3 & 4.

NCC-1F

MOM-4

TB3 OR TB4

NIM-1R / NIM-1W

1

2

3

4

TO ADDITIONAL

NIM-1Rs, NIM-1Ws,

NCC-1Fs OR NIC-Cs

NOTES:
1. No EOLR required for NIC-C.
2. 18 AWG min., 12 AWG max.
3. 80 Ohms max. per pair.

Unshielded twisted pair - .5μF line to line
Shielded twisted pair - .3μF line to line, .4μF line to
shield

4. Use twisted pair or twisted shielded pair.
5. Terminate shields at one end only.
6. Power limited to NFPA 70 per NEC 760.
7. CC-5 terminals 9 - 14 are not connected and can be

used to tie shields together.

8. Maximum voltage 8V P-P.
9. Each pair independently supervised.

Refer to Wiring Specification for MXL, MXL-IQ
and MXLV Systems, P/N 315-092772 revision
6 or higher, for additional wiring information.

Содержание NCC-1F

Страница 1: ...ses this does not need to be changed If COM 2 is not available Installation Instructions Model NCC 1F NCC G XNET Interface use Table 1 to select the desired COM port Be sure to configure the NCC G computer to use the same port and IRQ for XNET communications See Figure 1 for the location of the jumpers Figure 1 NCC 1F Module Board TABLE 1 CONFIGURING THE NCC 1F COM JP1 JP2 ADDRESS JP3 IRQ 1 A C 3F...

Страница 2: ...T The XNET connections are made on terminals 1 4 of the terminal block on the rear of the NCC 1F The primary pair or network A is on terminals 1 and 2 The secondary pair or network B is on terminals 3 and 4 For Style 4 networks install a 120 ohm EOLR on terminals 3 and 4 See Figure 2 for wiring details For Style 7 networks connect to both the primary and secondary pairs See Figure 2 for wiring det...

Страница 3: ...NCC 1F Ground fault detection must be enabled at a NIM 1R 1W or NIC C Select one and only one NIM 1R 1W or NIC C in the system where the ground fault is to be detected You must locate the NIM 1R 1W in a cabinet with either an MMB SMB or a PSR 1 See Figure 3 for the wiring diagram If the XNET is divided into multiple sections of copper wire using fiber optic segments ground fault detection can be e...

Страница 4: ...P N 315 095965 8 Siemens Industry Inc Building Technologies Division Florham Park NJ Siemens Building Technologies Ltd Fire Safety Security Products 2 Kenview Boulevard Brampton Ontario L6T 5E4 Canada ...

Отзывы: