OPERATION

The Model NCC-1F from Siemens Industry,
Inc., provides the NCC-G computer with a
direct RS-485 connection to the SIEMENS
XNET, eliminating the requirement that the
NCC-G computer be located within 25 feet of
an NIM-1R/1W. The NCC-1F operates in both
Style 4 and Style 7 modes.

The module installs in the NCC-G computer
and requires an empty 16-Bit ISA slot. The
NCC-1F can be set to any standard PC COM
port address and interrupt.

CONFIGURATION

The NCC-1F comes from the factory config-
ured as COM 2. In most cases this does not
need to be changed. If COM 2 is not available,

Installation Instructions

Model NCC-1F
NCC-G XNET Interface

use Table 1 to select the desired COM port. Be
sure to configure the NCC-G computer to use the
same port and IRQ for XNET communications.
See Figure 1 for the location of the jumpers.

Figure 1

NCC-1F Module Board

TABLE 1

CONFIGURING THE NCC-1F

COM

JP1 JP2 ADDRESS

JP3 (IRQ)

 1*

A

C

3F8-3FF

  4

 2*

A

D

2F8-2FF

  3

 3

B

C

3E8-3EF

  4

 4

B

D

2E8-2EF

  3

* Be sure to disable the NCC-G computer's internal

COM port or hardware conflicts will result.

Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ

Siemens Building Technologies, Ltd.
Fire Safety & Security Products
2 Kenview  Boulevard
Brampton, Ontario
L6T 5E4 Canada

Содержание NCC-1F

Страница 1: ...ses this does not need to be changed If COM 2 is not available Installation Instructions Model NCC 1F NCC G XNET Interface use Table 1 to select the desired COM port Be sure to configure the NCC G computer to use the same port and IRQ for XNET communications See Figure 1 for the location of the jumpers Figure 1 NCC 1F Module Board TABLE 1 CONFIGURING THE NCC 1F COM JP1 JP2 ADDRESS JP3 IRQ 1 A C 3F...

Страница 2: ...T The XNET connections are made on terminals 1 4 of the terminal block on the rear of the NCC 1F The primary pair or network A is on terminals 1 and 2 The secondary pair or network B is on terminals 3 and 4 For Style 4 networks install a 120 ohm EOLR on terminals 3 and 4 See Figure 2 for wiring details For Style 7 networks connect to both the primary and secondary pairs See Figure 2 for wiring det...

Страница 3: ...NCC 1F Ground fault detection must be enabled at a NIM 1R 1W or NIC C Select one and only one NIM 1R 1W or NIC C in the system where the ground fault is to be detected You must locate the NIM 1R 1W in a cabinet with either an MMB SMB or a PSR 1 See Figure 3 for the wiring diagram If the XNET is divided into multiple sections of copper wire using fiber optic segments ground fault detection can be e...

Страница 4: ...P N 315 095965 8 Siemens Industry Inc Building Technologies Division Florham Park NJ Siemens Building Technologies Ltd Fire Safety Security Products 2 Kenview Boulevard Brampton Ontario L6T 5E4 Canada ...

Отзывы: