MJ-X Communications Module
23
3. To change the value of the parameter, press the Change key, and then use the scroll keys to toggle the choices
or set the value for the parameter. Press the Save key after changing the value of a menu item to enter the
changes, or press the Cancel Reset key to cancel the change.
Each time a configuration menu item is changed, the main MJ-X Control Panel resets the communications module.
This reset is part of the process of updating the communications module with the new configuration.
Table 6-4 Communications Menu Items
Menu Item
Description
Selections
Data Stat = XXXXX
Data Port status
Not Applicable (This is a Status
Item)
DatPortBaud
Data Port baud (in bits/second)
300, 1200, 2400, 4800, 9600, 19200
Data Parity
Data Port parity
None, Even
Reg Id
Regulator Identification
0 - 32,766
Protocol
Communications Module protocol
DNP3.0, 2200, 2200NOA, MJ3A A,
MJ3A B1, MJ3A B2, 2179,
2179MJ-X, 2179 5A, SPECIAL
Comm Baud
Communications Module baud (transmission rate)
300, 1200, 2400, 4800, 9600, 19200
Comm Parity
Communications Module parity
None, Odd, Even
Comm Addr
Communications Module address
0 – 65,535
Resync Time
Communications Module resync time (in
characters)
0-250
Tx En Delay
Communications Module Transmit Enable Delay
(in milliseconds)
0-250
DNP dl Confirm
Confirm DNP Data Link
No, Yes
CM SW Repeat En
Enable software auto-repeat in Comm Module
No, Yes
CM Vers
Communications Module software version
X.XX