MJ-X Communications Module
20
Data
GND
RS-485 Twisted-Pair Cable
RS-485 Twisted-Pair Cable
Shield attached
at this end only
Shield grounded
at other end only
From RTU or other device
To next device
MJ-X Communications Module
Figure 6-2 RS-485 Connection
6.2.3 RS-485
Connector
The required connector for connecting to the MJ-X RS-232/485 Communications Module is the Phoenix Contact
Screw Terminal Block MSTBT 2,5/8-ST-5,08 or equivalent. Wire the connector as shown in Figure 6-2. This
connector is supplied with the communications module and is shown in Figure 6-3.
.3"
12 Gauge Wire
Maximum
Phoenix Contact Connector
COMBICON MSTB2,5/8-ST-5,08
Figure 6-3 Screw Terminal Block Connector
6.3 RS-232
Connections
The following section describes the connection requirements for RS-232 cable. This cable will allow you to connect
the MJ-X Control Panel to an RTU or personal computer.
Five of the standard RS-232 wires are used for this application.
•
Signal Return (RTN)
•
RXD
•
TXD
•
CTS
•
RTS
Table 6-2 lists the connections that must be made to connect the MJ-X RS232/485 Communications Module to a
personal computer, RTU, or other supervisory device. The MJ-X Communications Module defaults to
no-handshaking-required mode. However, the communications module asserts RTS while it transmits data, but the
module will ignore the CTS input signal.