Appendix
A.3 Technical specifications of MindConnect IoT2040
Getting Connected to MindSphere
84
Getting Started, 05/2018
A.3
Technical specifications of MindConnect IoT2040
Functions
Field protocol – S7
Siemens S7 (for S7-3xx / S7-4xx / ET-200s PLCs)
Field protocol – OPC UA
Part 8 of the OPC UA specification (Data Access)
Configuration of data collection
With Asset Configuration tool in MindSphere
Data buffering
Up to 500 MB buffering space for collected data
Proxy support
Yes
DHCP support
Yes
Security
Connection outbound via HTTPS on port 443 to MindSphere only; no incoming
connection accepted SSL/TLS encryption of data in transit to MindSphere
Installation type/mounting
Design
IoT Gateway, built-in unit
Mounting
DIN rail, wall mounting
Supply voltage
Type of supply voltage
DC 9…36 V, no galvanic isolation
Mains buffering
Mains/voltage failure stored energy
time
5 ms
Interfaces
USB port
1x USB 2.0, 1x USB client
Connection for keyboard/mouse
USB / USB
serial interface
2x COM ports (RS 232, RS 485)
Industrial Ethernet
Industrial Ethernet interface
2 x Ethernet (RJ45)
100 Mbps
Yes
1000 Mbps
No
Monitoring functions
Watchdog
Yes
Status LEDs
Yes
EMC
Interference immunity against discharge of static electricity
Interference immunity against
discharge of static electricity
±4 kV contact discharge acc. to IEC 61000-4-2; ±8 kV air discharge acc. to IEC
61000-4-2
Содержание MindConnect IoT2040
Страница 15: ...Overview of MindConnect Elements Getting Connected to MindSphere Getting Started 05 2018 15 ...
Страница 16: ......
Страница 30: ......
Страница 40: ......
Страница 65: ...Configuring data in Asset Manager 7 4 Datamapping Getting Connected to MindSphere Getting Started 05 2018 65 ...
Страница 66: ......
Страница 74: ......
Страница 91: ...Appendix A 6 List of abbreviations Getting Connected to MindSphere Getting Started 05 2018 91 ...
Страница 92: ......