Page 4
Milltronics ILE-37 – INSTRUCTION MANUAL
7ML19985CW01
Installation
The ILE-37 sensing head is available in two models: side mount and base mount. The
base mount version should be used if the flowmeter will be subjected to excessive
vibration, for flow rates below 1 t/h, or if handling product temperatures above 60 °C.
The side mount version is factory-installed on Siemens Milltronics flowmeters
designed for side mount sensing heads.
Side Mount
1.
With the flowmeter housing installed, remove the ILE-37 sensing head cover.
2.
Loosen the four ILE-37 mounting bolts.
3.
Place a spirit level on the flat top of the ILE-37 frame: adjust the sensing head level
by rotating it, and retighten the mounting bolts.
Base Mount
1.
With the flowmeter housing installed, mount the ILE-37 to a rigid support structure.
2.
With the outer gasket in place, bolt the ILE-37 to the housing.
3.
Adjust the sensing head levelling hardware provided, to establish level in both
horizontal planes.
Note:
Ensure that the structure used to support the base mount sensing head is
capable of supporting the dynamic material impact forces as well as the static weight
of the sensing head.
mounting
bolts
spirit level
spirit level
rigid
support
moving
beam
supporting/
levelling
bolts
front view
side view