37
Parameter
Function
Range
[Default]
Description / Notes
P928
••••
Local or Remote
control of drive
0 – 3
[0]
Specific to PROFIBUS-DP/CAN. See PROFIBUS / CAN
Handbooks for further details. (Access only possible
with P099 = 1 or 2).
Determines which interface has control of the drive. Note
that the drive status can always be monitored.
0
= Drive control and setpoint source is local.
1
= Drive control and setpoint source is via Comms
Module.
2
= Drive control is local and setpoint source is via
Comms Module.
3
Drive control is via Comms Module and setpoint
source is local.
P930
Most recent fault code
0 – 9999
[-]
The last recorded fault code
(see Section 6.3)
is stored in
this parameter. It is cleared when the inverter is
reset(P944=1).
P931
Most recent warning
type
0 – 9999
[-]
The last recorded warning is stored in this parameter until
power is removed from the inverter:
002
= Current limit active
004
= Slip limit exceeded
005
= Inverter over temperature (internal PTC)
006
= Motor overtemperature(I²T)
007
= Undervoltage
010
..=..P10+/P15V/SK200 +5V Power Supply Fault
018
= Auto restart after fault(P018) is pending. The
inverter may start at any time.
P944
Reset to factory default
settings
0 – 1
[0]
Set to ‘1’ and then press
P
to reset all parameters except
P101 to the factory default settings.
P947
Specific to PROFIBUS-DP. See PROFIBUS Handbook for
further details. (Access only possible with P099 = 1).
P958
Specific to PROFIBUS-DP. See PROFIBUS Handbook for
further details. (Access only possible with P099 = 1).
P960
Protocol Type
0 – 3
[0]
(SW
Version :
3.00
onwards)
Specific to PROFIBUS-DP/CAN. See PROFIBUS / CAN
Handbooks for further details. (Access only possible
with P099 = 1 or 2).
Selects the CANbus protocol.
0
= CAN communication disabled.
1 =
CANopen communication enabled.
2
=CAN masterdrive commmunication enabled
(future).
3
= DeviceNet communication enabled (future).
P962
(SW
Version :
3.00
onwards)
Specific to CAN. (Access only possible with P099 = 2).
P963
(SW
Version :
3.00
onwards)
Specific to CAN (Access only possible with P099 = 2).
P964
(SW
Version :
3.00
onwards)
Specific to CAN (Access only possible with P099 = 2).