Issue 07/04
3 Functions
MICROMASTER 420 Operating Instructions
6SE6400-5AA00-0BP0
93
NOTE
When the filter time constant P0753 (ADC-PT1) is increased, this smoothes the
ADC input signal therefore reducing the ripple. When this function is used within a
control loop, this smoothing has a negative impact on the control behavior and
immunity to noise (the dynamic performance deteriorates).
Wire breakage monitoring
The wire breakage monitoring (refer to Fig. 3-25) is set using parameters P0756
and P0761. If the input signal of the analog input falls below the wire breakage
threshold (0.5 * P0761), then after the time in P0762 expires, fault F0080 is output
and the status bit is set in parameter r0751.
t
0
Signal loss
t
0
P0761
V
1
P0761
0,5
⋅
10
P0762
r0751
t
0
1
F0080
Fault acknowl.
Analog input
t
0
Act. ADC after scaling
r0755
Fig. 3-26
Wire breakage monitoring
The following secondary conditions/limitations apply to the wire breakage
monitoring:
The monitoring function must be activated using parameter P0756
Width of the ADC dead zone P0761 > 0
Wire breakage monitoring if the ADC input quantity
≤
0.5 * P0761
Note
The wire-breakage monitoring function is only possible for unipolar analog
inputs.
Input range 0 to 0.5 * P0761 of the analog input must be excluded when
activating the wire breakage monitoring for normal operation.
Содержание MICROMASTER 420
Страница 10: ...Safety Instructions Issue 07 04 MICROMASTER 420 Operating Instructions 10 6SE6400 5AA00 0BP0 ...
Страница 16: ...Table of Contents Issue 07 04 MICROMASTER 420 Operating Instructions 16 6SE6400 5AA00 0BP0 ...
Страница 34: ...2 Installation Issue 07 04 MICROMASTER 420 Operating Instructions 34 6SE6400 5AA00 0BP0 ...
Страница 156: ...4 Troubleshooting Issue 07 04 MICROMASTER 420 Operating Instructions 156 6SE6400 5AA00 0BP0 ...
Страница 166: ...6 Options Issue 07 04 MICROMASTER 420 Operating Instructions 166 6SE6400 5AA00 0BP0 ...
Страница 188: ...MICROMASTER 420 Operating Instructions 188 6SE6400 5AA00 0BP0 ...