6SE6400-5AA00-0BP0
3.21.1.3 Slip
compensation
Parameter range:
P1335 – r1337
Warnings -
Faults -
Function chart number:
FP6100
In the V/f characteristic operating mode the motor frequency is always lower than
the drive inverter output frequency by the slip frequency f
s
. If the load (the load is
increased from M
1
to M
2
) is increased with a constant output frequency, then the
slip s when motoring increases and the motor frequency decreases (from f
1
to f
2
).
This behavior, typical for an induction motor, can be compensated using slip
compensation P1335. This therefore eliminates the speed reduction, caused by the
load, by boosting (increasing) the drive inverter output frequency (refer to Fig.
3-62).
Without Slip compensation
M
f
∆
f
f
2
f
1
M
2
M
1
With Slip compensation
M
f
∆
f
f
2
f
1
M
2
M
1
f
out M1
f
out M2
Fig. 3-62
Slip compensation
Содержание MICROMASTER 420
Страница 10: ...Safety Instructions Issue 07 04 MICROMASTER 420 Operating Instructions 10 6SE6400 5AA00 0BP0 ...
Страница 16: ...Table of Contents Issue 07 04 MICROMASTER 420 Operating Instructions 16 6SE6400 5AA00 0BP0 ...
Страница 34: ...2 Installation Issue 07 04 MICROMASTER 420 Operating Instructions 34 6SE6400 5AA00 0BP0 ...
Страница 156: ...4 Troubleshooting Issue 07 04 MICROMASTER 420 Operating Instructions 156 6SE6400 5AA00 0BP0 ...
Страница 166: ...6 Options Issue 07 04 MICROMASTER 420 Operating Instructions 166 6SE6400 5AA00 0BP0 ...
Страница 188: ...MICROMASTER 420 Operating Instructions 188 6SE6400 5AA00 0BP0 ...