3 Functions
Issue 07/04
MICROMASTER 420 Operating Instructions
90
6SE6400-5AA00-0BP0
3.6.2
Digital output (DOUT)
Number: 1
Parameter range:
r0730 – P0748
Function chart number:
FP2100
Features:
- cycle time:
1 ms
Binary states in the drive can be output via the digital output. As result of the fast
cycle time, it is possible to control external devices and to display the state in real
time. In order that higher powers can also be output, the internal signal (TTL level)
is amplified using a relay (refer to Fig. 3-23).
Relay:
- max. opening / closing time:
5 / 10 ms
- voltage / current
30 V DC / 5 A
250 V AC / 2 A
(52:7)
BI: Fct. of DOUT 2
P0732.C
-1
0
2
Invert DOUTs
0 ... 7
P0748 (0)
CO/BO: State DOUTs
r0747
r0747
NO
COM
Kl.11
Kl.10
.1
Fig. 3-23
Digital output
The states, which are to be output, are defined using the "BI" parameter P0731
(digital output). For the definition, the "BO" parameter number or "CO/BO"
parameter number and the bit number of the particular state should be entered into
P0731. Frequently used states including the parameter number and bit are shown
in the following Table (refer to Table 3-11).
Содержание MICROMASTER 420
Страница 10: ...Safety Instructions Issue 07 04 MICROMASTER 420 Operating Instructions 10 6SE6400 5AA00 0BP0 ...
Страница 16: ...Table of Contents Issue 07 04 MICROMASTER 420 Operating Instructions 16 6SE6400 5AA00 0BP0 ...
Страница 34: ...2 Installation Issue 07 04 MICROMASTER 420 Operating Instructions 34 6SE6400 5AA00 0BP0 ...
Страница 156: ...4 Troubleshooting Issue 07 04 MICROMASTER 420 Operating Instructions 156 6SE6400 5AA00 0BP0 ...
Страница 166: ...6 Options Issue 07 04 MICROMASTER 420 Operating Instructions 166 6SE6400 5AA00 0BP0 ...
Страница 188: ...MICROMASTER 420 Operating Instructions 188 6SE6400 5AA00 0BP0 ...