background image

1 Task 

 
 

Frei verwendbar House Control with Master-Slave - LOGO! Set 9 
Entry ID: 64143308,    V2.2,    09/2018 

 

 

 

©

 S

ie

m

e

n

s

 A

G

 2018

 A

ll

 r

ig

h

ts

 r

e

s

e

rv

e

d

 

Task 

Introduction 

In residential house, the following functions shall be controlled manually or 
automatically: 

 

Blinds and Roof hatch (up/down) 

 

Interior and exterior lighting (on/off) 

 

Heater 

 

Garden watering 

 

Figure 1-1 

Roof hatch

(up/down)

Interior light 

(on/off)

Blinds

(up/down)

Exterior light

(on/off)

Central light

(on/off)

Blinds

(up/down)

Heizung

PT 100

 

 
It shall be possible with a selector button to preset for each function whether it is 
controlled automatically or manually. 

If automatic control is set, the blinds shall open or close automatically and the 
garden watering is to be activated or deactivated depending on time and day. 
Simultaneously, the roof hatches shall open or close and the heating shall switch 
on or off depending on the temperature. 

If the maintenance mode is set for the blinds, manual or automatic closing shall be 
blocked. 

The status of each of the house functions shall be displayed on the spot and in 
addition with a mobile device (tablet or smartphone). 

At the same time it shall be possible to control the house functions with the mobile 
device.

Содержание LOGO! 8

Страница 1: ...Frei verwendbar House Control with Master Slave Communication LOGO 8 Set 9 https support industry siemens com cs ww en view 64143308 Siemens Industry Online Support ...

Страница 2: ...tions Claims for damages arising from a breach of material contractual obligations shall however be limited to the foreseeable damage typical of the type of agreement unless liability arises from intent or gross negligence or is based on loss of life bodily injury or damage to health The foregoing provisions do not imply any change in the burden of proof to your detriment You shall indemnify Sieme...

Страница 3: ...ing the master slave mode 19 3 3 2 Assigning an IP address to LOGO TDE 20 3 3 3 Selecting LOGO with the LOGO TDE 20 3 3 4 PC 20 3 3 5 IP addresses and subnet masks 21 3 4 Downloading a program into LOGO 8 21 3 5 Setting web server access 23 3 6 User defined Webserver LOGO V8 2 25 3 7 Adjust the runtime of the blinds in the LOGO program 27 4 Operating the Application Example 29 4 1 Operation with b...

Страница 4: ...ble with a selector button to preset for each function whether it is controlled automatically or manually If automatic control is set the blinds shall open or close automatically and the garden watering is to be activated or deactivated depending on time and day Simultaneously the roof hatches shall open or close and the heating shall switch on or off depending on the temperature If the maintenanc...

Страница 5: ...nal extension modules were deployed for each LOGO module This makes it possible to add further inputs and outputs of the house control at any time via DM16 24R 3 or DM8 24R 4 expansion modules The LOGO expansion module AM2 AQ 5 is used to add two analog outputs to the house control One PT100 and one PT1000 temperature sensor respectively is connected to the RTD expansion module 6 The temperature s...

Страница 6: ... enables to control the blinds lights and roof hatch and to display their current status with a tablet 9 smartphone or PC using the integrated web server of the LOGO 8 A LOGO power supply 10 with 24V is used in the automation solution A circuit breaker provides the necessary protection Additionally the power supply for a individual line of the distributor box can be switched off with miniature cir...

Страница 7: ...4R 2 6ED1055 1HB00 0BA2 5 LOGO AM2 AQ 1 6ED1055 1MM00 0BA2 6 LOGO AM2 RTD 1 6ED1055 1MD00 0BA2 7 LOGO TDE 1 6ED1055 4MH08 0BA0 8 WLAN Access Point 1 Available from specialist retailers Technical specifications Standard IEEE 802 11 WLAN speed up to 150Mbps 9 Tablet PC 1 Available from specialist retailers 10 LOGO POWER 24V 2 5 A 1 6EP3332 6SB00 0AY0 11 PT100 temperature sensors 1 Available in speci...

Страница 8: ...ave_DOC_v22_en pdf This document 2 3 House functions 2 3 1 Blinds Inputs and outputs Table 2 4 No Hardware LOGO module Program inputs outputs 1 Blinds button left up make contact Master I1 I1 2 Blinds button left down make contact Master I2 I2 3 Blinds button right up make contact Master I3 I3 4 Blinds button right down make contact Master I4 I4 5 Blinds motor left up Master Q1 Q1 6 Blinds motor l...

Страница 9: ...ogrammed to open or close completely A change of direction during travel is possible by activating the other direction The LOGO TDE or the LOGO display can be used to predefine manual or automatic control of the blinds In manual mode the blinds can be controlled with buttons or with the cursor keys over the LOGO controller and the LOGO TDE In addition the blinds can be controlled with a tablet sma...

Страница 10: ...ay or LOGO TDE is available in the LOGO manual in Chapter Configuring LOGO Table 2 5 No Function Function block Block name in the program 1 Moving blinds up down on weekends Weekly timer weekend 2 Moving blinds up down Monday to Friday Weekly timer weekday 3 Moving blinds up down at sunrise sunset Astronomical clock astro clock 4 Time delay for automatic opening closing of the blinds Random genera...

Страница 11: ...y can be used to predefine manual or automatic control of the roof hatch In manual mode the roof hatch can be controlled on the spot with a button In addition in manual mode the roof hatch can be controlled remotely over a tablet smartphone or PC with the F1 function key over the integrated webserver of LOGO 8 In automatic mode the roof hatch is controlled with the PT100 see Table 2 8 depending on...

Страница 12: ...n description With the LOGO display and LOGO TDE it is possible to set a setpoint value for each room If the room temperature reaches the setpoint value the heating is switched off If the room temperature falls 1 below the setpoint value the heating is switched on again Table 2 9 No Function Function block Block name in the program 1 Temperature dependent on off heating 1 Analog Comparator heater ...

Страница 13: ...TDE If required parameters like days and times for garden watering can be adjusted Table 2 10 No Function Function block Block name in the program 1 Daily automatic garden watering Weekly timer watering 2 3 5 Interior and exterior lighting Inputs and outputs Table 2 11 No Hardware LOGO module Program inputs outputs 1 Button light on off room 1 integrated panic button Slave I1 NI1 network input 1 2...

Страница 14: ...egrated webserver of LOGO 8 The panic mode is activated when one of the light buttons is pressed for at least 3 seconds All lights are switched on The panic mode is deactivated when one of the light buttons is pressed for at least 3 seconds again All lights are switched off The panic mode is automatically deactivated with a time delay of 30 minutes Table 2 12 No Function Function block Block name ...

Страница 15: ...OGO The table below describes the LOGO program settings for this Table 2 13 No Action response LOGO Soft Comfort V8 1 Start LOGO Soft Comfort V8 2 Click in the Mode bar on Network Project to open the project mode 3 Click on Add new device The subsequent window enables you to add devices you want to use to the network in this example a master and a slave LOGO 4 The Network view gives you an overvie...

Страница 16: ...LOGO in the program select a digital Network input from the Instructions tree and add it to your switching program 7 Then double click on the digital Network input in the program to open its block properties 8 Perform the following steps in the block properties 1 Select the Remote device item 2 The slave LOGO that you have already added to the network view before now automatically appears under De...

Страница 17: ... and a data transfer mechanism between the master and the slave LOGO Note If the digital network input is displayed in red the communication between master and slave LOGO is not available anymore 11 A connecting line has automatically been created between master and slave LOGO which means that both devices are communicating with each other Note Double click on the connecting line to open the conne...

Страница 18: ...ther information is available in the LOGO manual in chapter LOGO installation and wiring 3 1 2 WLAN Access Point Connect the WLAN Access Point to the network with your LOGO devices via Ethernet e g via LOGO CSM Further information is available in the manual of the WLAN Access Point Note Make sure that your WLAN Access Point and the LOGO have the same basis address For example IP address master LOG...

Страница 19: ... LOGO 8 and press OK 2 Select IP address 3 Press the OK button of the LOGO controller and use the cursor keys C1 C2 C3 and C4 to enter your master LOGO s IP address here 192 168 1 10 Confirm with the OK button 4 Press the ESC key to return to the previous menu item and select Set M S mode 5 For configuring the master LOGO select Master 6 Repeat steps 1 5 for the configuration of the slave LOGO wit...

Страница 20: ...he password LOGO is set by default Further information is available in the LOGO Manual in Chapter Configuring menu access protection in LOGO 3 3 3 Selecting LOGO with the LOGO TDE To be able to operate the application example with the LOGO TDE the master LOGO must be selected according to its IP address in the LOGO TDE More information on how to select a LOGO with the LOGO TDE menu can be found in...

Страница 21: ...s are designed for 24V technology If a combination of 230V and 24V is required a 230V basic device must be used Between a 230V basic device and a 24V expansion module an analog module for potential separation must be used 3 4 Downloading a program into LOGO 8 Together with this application example a completed LOGO program for LOGO 8 is offered for download The table below contains a description on...

Страница 22: ...GO password 6 Click Yes to set the LOGO to STOP before the download 7 Acknowledge the warning message The diagram exceeds BM location memory limit with OK Note The LOGO controller has an internal layout memory of 30000 Byte If more than 30000 Bytes are required for the graphical information then the included information is reduced to the right positioning of the function blocks in the diagram If t...

Страница 23: ...g the LOGO Soft Comfort V8 menu Start LOGO Soft Comfort V8 and make the following settings Table 3 4 No Action response LOGO Soft Comfort V8 1 In the menu navigate to Tools Transfer Access Control 2 Select the interface for your connection to LOGO and enter the IP address of your LOGO Click Test in order to check whether the connection has been established successfully If the connection is success...

Страница 24: ...143308 V2 2 09 2018 24 Siemens AG 2018 All rights reserved No Action response LOGO Soft Comfort V8 4 Navigate to the Web server access item and tick the box for Allow Web server access 5 Acknowledge the warning message with Yes 6 Tick Enable password protection for Web server access and enter a password ...

Страница 25: ...following devices and browsers PCs with all compatible web browsers All smartphones optimized resolution All compatible web browsers Tablet PCs optimized resolution All compatible web browsers 3 6 User defined Webserver LOGO V8 2 Since version 8 2 LOGO 8 offers a user defined web server The web project is created with the LOGO web editor LWE and loaded onto a Micro SD card Note You will find instr...

Страница 26: ... the web editor were linked to a counter in the LOGO circuit program Note The bar charts were rotated 180 because the roller blind is white and the open window is black A color change of the white area in the bar chart is not possible in this version of the Web Editor V1 0 The button for the panic function 3 is linked to a static image in the idle state If the button is pressed in the web browser ...

Страница 27: ...tion response KTP700 display 1 1 Unzip and execute the LOGO Soft Comfort V8 project from the download 2 Open the master program by double clicking it 2 1 Move blinds up see Table 4 2 2 Note down the runtime 3 1 Navigate in the program to the function blocks B006 B013 B010 and B030 2 With a double click on the respective block the block properties are being opened 3 Set in the block properties of t...

Страница 28: ...n response KTP700 display 6 1 Go to function block B161 and open the block properties with a double click 2 Double click on the bar graph to get to its parameters 3 Set the maximum value to the value you noted down in item 5 4 Save the settings with OK Now the bar graph display for the LOGO display and LOGO TDE has been set 7 Load the modified program to the master LOGO ...

Страница 29: ...ure that you don t control in mixed operation on the HW as well as on the webserver Decide before you begin with the operation of the application example if you want to control either over the cursor keys on the LOGO controller and on the LOGO TDE or over the F keys on the webserver If this requirement is not observed property damage or personal injury may occur 4 1 Operation with buttons Inputs f...

Страница 30: ...ntry ID 64143308 V2 2 09 2018 30 Siemens AG 2018 All rights reserved 4 2 Menu overview for the control of the house functions with the LOGO TDE or LOGO display Table 4 1 No Description LOGO display and LOGO TDE 13 Main menu 14 Blinds Change mode 15 Blinds Maintenance mode 16 Blinds Central control ...

Страница 31: ... Control with Master Slave LOGO Set 9 Entry ID 64143308 V2 2 09 2018 31 Siemens AG 2018 All rights reserved No Description LOGO display and LOGO TDE 17 Lights Central control 18 Lights Change mode 19 Hatch roof Change mode 20 Hatch roof Auto mode 21 Watering ...

Страница 32: ...ng message is displayed on the LOGO display and on the LOGO TDE that all lights are on At the same time the LOGO display lights up orange On the webserver the display also lights up orange as long as the panic function is activated The warning message for the panic function is not displayed on the webserver As soon as the panic function is deactivated the warning message must be acknowledged in bo...

Страница 33: ...he blind control menu 2 Press ESC C1 All blinds move up 3 While the blinds travel upwards press ESC C2 The blinds are stopped 4 Now press ESC C2 0 5 seconds The blinds now move downwards again i e in reverse direction 4 3 Activating the panic function for the lights Table 4 3 No Action response LOGO display and LOGO TDE 1 Press one of the light buttons in the house for more than 3 seconds All ligh...

Страница 34: ...3 seconds again The panic function has now been deactivated 3 Acknowledge the warning message with OK on the LOGO or with ENTER on the LOGO TDE Note As in the LOGO Program two character sets are activated for the message texts are enabled messages in both character sets must be acknowledged in order to hide them 4 4 Operation using the web server menu overview Table 4 4 No Description Display on t...

Страница 35: ... IP address of your master LOGO here 192 168 1 10 2 Enter the password that you have specified in Tools Transfer Access control in LOGO Soft Comfort V8 see Chapter 3 5 Table 3 4 step 6 3 Click on the Log On button 2 1 Click LOGO TDE to open the virtual display of LOGO TDE The first screen in the menu for web server operation opens 2 Press the F4 button until you get to the light operation screen 3...

Страница 36: ...ronized with the corresponding block in the circuit program Synchronization takes place when the end position of a roller blind is reached Figure 4 1 1 5 6 7 9 3 4 2 8 Table 4 6 Lfd Nr Funktion Bemerkung 1 Roller blind high Roller blind is being lifted up to roller blind limit switch 2 Roller blind from Roller blind is being lowered up to roller blind limit switch 3 Roller blind Roller blind is up...

Страница 37: ...lication examples and videos all information is accessible with just a few mouse clicks https support industry siemens com SITRAIN Training for Industry We support you with our globally available training courses for industry with practical experience innovative learning methods and a concept that s tailored to the customer s specific needs For more information on our offered trainings and courses...

Страница 38: ...load page of the entry https support industry siemens com cs ww en view 64143308 3 LOGO 8 Manual https support industry siemens com cs ww en view 109741041 4 LOGO Software updates http w3 siemens com mcms programmable logic controller en logic module logo demo software Pages Default aspx 5 LOGO Application Examples http w3 siemens com mcms programmable logic controller en logic module logo applica...

Отзывы: