6/16
CC1N7421E
December 04, 1998
Landis & Staefa Division
Operating voltage
AC 230 V +10 % / -15 %
Weight
- Burner control
approx. 158 g
Mains frequency
50 Hz -6 %...60 Hz +6 %
- Plug-in base AGK11
approx. 80 g
- AGK65...
approx. 12 g
Power consumption
12 VA
- AGK66...
approx. 12 g
Primary fuse
max. 10 A (slow)
Degree of protection
IP 40
Mounting position
optional
Max. cable length terminals 8 and 10
20 m
Environmental conditions
Input current at terminal 12
max. 5 A
Transport
IEC 721-3-2
Climatic conditions
class 2K2
Identification code to EN 298
Temperature range
-40...+60 °C
LMG21... / LMG22...
F T L L X N
Humidity
< 95 % r.h.
LMG25...
F T C L X N
Mechanical conditions
class 2M2
Operation
IEC 721-3-3
CE conformity
Climatic conditions
class 3K5
According to the directives of the European Union
Temperature range
-20...+60 °C
Electromagnetic compatibility EMC
Humidity
< 95 % r.h.
89 / 336 EEC incl. 92 / 31 EEC
Condensation, formation of ice and ingress of
water are not permitted!
Directive for gas appliances
90 / 396 EEC
Terminal rating
At cos
ϕ
≥
0.6
At cos
ϕ
= 1
- Terminal 3
max. 2.7 A
(15 A during max. 0.5 s)
max. 3 A
- Terminals 4, 5 and 7
max. 1.7 A
max. 2 A
- Terminal 10
max. 1 A
max. 1 A
Technical data
LMG2...