Building Technologies
CC1N7101en
HVAC Products
29.06.2006
Type summary
(other types of burner controls on request)
The type references given below apply to the LME… burner control without plug-in
base and without flame detector. For ordering information on plug-in bases and other
accessories, refer to «Ordering».
Flame detector
Type
reference
Main
voltage
tw
approx.
s
t1
min.
s
TSA
max.
s
t3n
approx.
s
t3
approx.
s
t4
approx.
s
t22
approx.
s
2)
t10
min.
s
3)
t11
min.
s
1)
t12
min.
s
1)
For
replacing of
Burner controls for 1-stage burners without communication (up to 120 kW output)
Ionization probe
(ION)
LME11.330A2
AC230V
2.5 30 3 2
2
---
--- 5 --- ---
Burner controls for 2-stage burners without communication, without actuator control
LME21.130A1
AC 120 V
2.5 7 3 2
2
8 --- 5 ---
---
LGB21.130A27
LME21.130A2
AC 230 V
2.5 7 3 2
2
8 --- 5 ---
---
LGB21.130A27
LMG21.130A27
LME21.230A2
AC 230 V
2.5 20 3 2
2
8
--- 5 --- ---
LGB21.230A27
LMG21.230A27
LME21.330A1
AC 120 V
2.5 30 3 2
2
8
--- 5 --- ---
LME21.330A2
AC 230 V
2.5 30 3 2
2
8
--- 5 --- ---
LGB21.330A27
LMG21.330A27
LME21.350A1
AC 120 V
2.5 30 5 4
2
10 --- 5 --- ---
LGB21.350A17
LME21.350A2
AC 230 V
2.5 30 5 4
2
10 --- 5 --- ---
LGB21.350A27
LMG21.350A27
Ionization probe
(ION) or flame
detector QRA...
with AGQ3...
LME21.550A2
AC 230 V
2.5 50 5 4
2
10 --- 5 --- ---
LGB21.550A27
LMG22.550B27
Burner controls for 2-stage burners without communication, with actuator control
LME22.131A2
AC 230 V
2.5 7 3 2
3
8 --- 3 12
12
LGB22.130A27
LMG22.130A27
LME22.232A2
AC 230 V
2.5 20 3 2
3
8
--- 3
16.5
16.5
LGB22.230A27
LMG22.230A27
LME22.233A2
AC 230 V
2.5 20 3 2
3
8
--- 3 30 30
LMG22.233A27
LME22.331A1
AC 120 V
2.5 30 3 2
3
8
--- 3 12 12
---
Ionization probe
(ION) or flame
detector
QRA...
4)
with
AGQ3...
LME22.331A2
AC 230 V
2.5 30 3 2
3
8
--- 3 12 12
LGB22.330A27
Burner controls for 2-stage burners
LME23.331A2
AC 230 V
2.5 30 3 2
3
8
--- 3 12 12
LGB32.330A27
Blue flame
detector QRC…
LME23.351A2
AC 230 V
2.5 30 5 4
1
10 --- 3 12 12
LGB32.350A27
Legend
tw
Waiting time
1)
Max. running time available for actuator «SA»
TSA
Safety time
The actuator running time must be shorter
t1
Prepurge time
2)
t22 + response time of flame relay
t3
Preignition time
3)
Max. 65 s
t3n
Postignition time
4)
Only used for AC 230 V
t4
Interval between ignition «Off» and «BV2»
t10
Specified time for air pressure signal
t11
Programmed opening time for actuator «SA»
t12
Programmed closing time for actuator «SA»
t22
2nd safety time