Mechanical design
•
Units of plug-in design like their predecessor types LGB... and LMG... (refer to
«Dimensions»)
•
The housing is made of impact-proof, heat-resistant and flame-retarding plastic. It
is of plug-in design and engages audibly in the base
•
The housing accommodates the
- microcontroller for the control sequence and the control relays for load control
- electronic flame signal amplifier (ionization)
- lockout reset button with its integrated 3-color signal lamp (LED) for operational
status and fault status messages and the socket for connecting the OCI400 inter-
face adapter
•
Multicolor indication for operational status and fault status messages
•
Transmission of operational status and fault status messages and detailed service
information via additional OCI400 interface adapter and ACS400 / ACS410 PC
Windows software
•
Burner capacity unlimited (thermal output on startup
≤
120 kW)
•
3 repetitions in the event of loss of flame during operation (LME11…)
LME...
Indication and
diagnostics
Versions