11/23
Building Technologies
CC1N7101en
HVAC Products
29.06.2006
Technical data
(cont´d)
Mains voltage
AC 230 V +10 % / -15 %
Mains frequency
50...60 Hz
±
6 %
Perm. cable length from QRA... to AGQ3…
(lay separate cable)
max. 20 m
Perm. cable length from AGQ3... to LME... max. 2 m
Weight of AGQ3...
approx. 140 g
Mounting position
optional
Degree of protection
IP 40, to be ensured through mounting
Power consumption
4.5 VA
At mains voltage U
N
AC 220 V
AC 240 V
Detector voltage at QRA... (with no load)
Terminal 3 off (refer to control sequence)
DC 400 V
DC 400 V
Terminal 3 on (refer to control sequence)
DC 300 V
DC 300 V
Detector voltage
Load by DC measuring instrument Ri > 10 M
Ω
Terminal 3 off (refer to control sequence)
DC 380 V
DC 380 V
Terminal 3 on (refer to control sequence)
DC 280 V
DC 280 V
DC current detector signals with UV detector
QRA...
Min. required
Max. possible
Measurement at the UV detector QRA…
200 µA
500 µA
In connection with LME… burner controls, use of UV ancillary unit AGQ3... is manda-
tory.
(A)
Correct functioning of aged UV cells can be checked as UV test with a higher
supply voltage across the UV cell after controlled shutdown until terminal 3 on.
Connection diagram
Measuring circuit for measuring the UV
detector current
12
2
3
1
71
01
a0
6/0
7
0
5
GP/SB
R/W
L
L
N
QRA...
+
-
br
bl rt
sw
AGQ3...
sw
bl
(A)
LME...
br
bl rt
sw
AGQ3...
sw
bl
QRA
7
1
0
1a0
7/
07
0
5
Measurement made at the UV detector
QRA…
C
Electrolytic capacitor 100...470 µF; DC 10...25 V
bl
Blue
M Microammeter
Ri max. 5,000
Ω
br
Brown
QRA... UV
detector
gr
Grey
GP Gas
pressure
switch
rt Red
SB
Safety limit thermostat
sw
Black
R
Control thermostat or pressurestat
W
Limit thermostat or pressure switch
Flame supervision
with AGQ3… and UV
detector QRA...
Ancillary unit AGQ3...
Legend