12/28
Building Technologies Division
CC1N7785en
20.11.2017
Technical data
Mains voltage
AC 230 V -15% / +10%
AC 100 V -15%...AC 110 V +10%
Mains frequency
50...60 Hz ±6%
Unit fuse, built-in
T6,3H250V to DIN EN 60 127
Primary fuse (external)
Max. 16 A (slow)
Weight
Approx. 1000 g
Power consumption
Approx. 3.5 VA
Perm. mounting position
Optional
Degree of protection
IP40, (to be ensured through mounting)
with the exception of the connection area
(terminal base)
Safety class
II
Perm. input current at terminal 1
Max. 5 A to VDE 0660 AC3
Perm. current load of control terminals
Max. 4 A to VDE 0660 AC3
Required switching capacity of switching
devices
-
Between terminals 4 and 5, 4 and 12
-
Between terminals 4 and 14
1 A, AC 250 V
depending on loading of terminals 15, 16,
18, 19 (LGK16...: 16...19), min. 1 A,
AC 250 V
Permissible length of the standard detector
cable (laid separately)
See
Technical data
, section
Flame
supervision
Capacity
-
Output on startup (without fan)
-
Nominal
output
Optional (with ignition < 120 kW)
Optional
Storage
DIN EN 60721-3-1
Climatic conditions
Class 1K3
Mechanical conditions
Class 1M2
Temperature range
-20...+60 °C
Humidity <95%
r.h.
Transport
DIN EN 60721-3-2
Climatic conditions
Class 2K3
Mechanical conditions
Class 2M2
Temperature range
-20...+60 °C
Humidity <95%
r.h.
Operation
DIN EN 60721-3-3
Climatic conditions
Class 3K3
Mechanical conditions
Class 3M3
Temperature range
-20...+60 °C
Humidity <95%
r.h.
Installation altitude
Max. 2,000 m above sea level
Caution!
Condensation, formation of ice and ingress of water are not permitted!
If this is not observed, there is a risk of loss of safety functions and a risk of
electric shock
General unit data
LOK16.../LGK16...
Environmental
conditions