GAMMA wave
Technical Product Information
February 2007
Switch actuator wave GE 561/01
5WG3 561-4AB01
Siemens AG
wave GE 561/01, 6 pages
Technical Manual
Automation and Drives Group
Electrical Installation Technology
©
Siemens AG 2007
Update: http://www.siemens.de/gamma
P.O. Box 10 09 53, D-93009 Regensburg
Subject to change without prior notice
2.20.8.1/1
Product- and Application Description
The switch actuator wave GE 561/01 is a 2-channel ac-
tuator with integrated KNX radio receiver/ transmitter
and a rating current of 2x16A for switching electric loads.
It can be controlled by up to 40 radio sensors that are
equipped with GAMMA wave radio technology and in-
corporated into a scene control with up to 16 scenes.
The switch actuator is connected to the 230-V network
and supplied with current via an integrated power sup-
ply. The connected loads are each switched via a relay
contact, it being adjustable whether the loads are to be
permanently switched on or off (normal operation) or
whether the actuator should function in time-switch op-
eration with an adjustable on-period from 1 to 60 min-
utes.
In the event of a failure of operational power the switch
state of both relays is maintained.
The GE device is embodied in an elongated design and
is suitable for installation in housing or under covers.
The switch actuator is put into operation without addi-
tional auxiliaries via a pushbutton installed on the top of
the device and an LED to display the operation condi-
tions in the “special function” operating mode.
The “Special Function” operating mode includes the fol-
lowing functions:
•
Connecting radio sensors with the function switching
“ON/OFF” or scene
•
Activating/deactivating the time switch function
•
Clearing connections to radio sensors
•
Resetting the device to the supplied state
Technical Specifications
Frequency band
•
868 MHz (transmission is not susceptible to interfer-
ence; frequency band reserved for system and secu-
rity applications)
Range of radio control
•
Approx. 100 m in clear area
Power supply
•
230V power supply via terminals 2 (L1) and 3 (N)
•
Rated voltage: AC 230V, 50 Hz
•
Protection via 16A circuit-breaker,
characteristic B or C required
Control elements
•
1 pushbutton: to switch between different operation
and commissioning conditions
Display elements
•
1 red LED: to display the operation conditions and
settings during commissioning
Outputs
•
Number: 2 (relay contacts)
•
Rated voltage: AC 230V
•
Rated current: 16A at cos phi = 1
Connections
•
5 screw terminals for power supply and load supply;
wire-stripping length approx. 7 … 8 mm
•
The following conductors or cross sections are per-
missible:
- 0.5 to 4 mm
2
single-wire
- 0.5 to 2,5 mm
2
finely stranded
Mechanical specifications
•
Housing:
plastic
•
Dimensions: device installation,
42 x 32 x 274.5 mm (W x H x L)
•
Weight: approx. 200 g
•
Fire load: approx. 5500 kJ
Electrical safety
•
Pollution degree (according to IEC 60664-1): 2
•
Protection (according to EN 60529): IP 20
•
Overvoltage category (according to IEC 60664- 1) III
•
Device
complies
with EN 60669-2-1
•
Relays
with
µ
contact