background image

 

GAMMA wave 

Technical Product Information 

February 2007 

Switch actuator wave GE 561/01 

5WG3 561-4AB01 

 

 

Siemens AG 

wave GE 561/01, 6 pages 

Technical Manual 

Automation and Drives Group 

 

 

Electrical Installation Technology 

©

 Siemens AG 2007 

Update: http://www.siemens.de/gamma 

P.O. Box 10 09 53, D-93009 Regensburg  

Subject to change without prior notice 

 

 

2.20.8.1/1 

 

Product- and Application Description 

 
 
 

 

 
 
 
The switch actuator wave GE 561/01 is a 2-channel ac-
tuator with integrated KNX radio receiver/ transmitter 
and a rating current of 2x16A for switching electric loads. 
It can be controlled by up to 40 radio sensors that are 
equipped with GAMMA wave radio technology and in-
corporated into a scene control with up to 16 scenes. 
 
The switch actuator is connected to the 230-V network 
and supplied with current via an integrated power sup-
ply. The connected loads are each switched via a relay 
contact, it being adjustable whether the loads are to be 
permanently switched on or off (normal operation) or 
whether the actuator should function in time-switch op-
eration with an adjustable on-period from 1 to 60 min-
utes. 
 
In the event of a failure of operational power the switch 
state of both relays is maintained. 
 
The GE device is embodied in an elongated design and 
is suitable for installation in housing or under covers. 
 
The switch actuator is put into operation without addi-
tional auxiliaries via a pushbutton installed on the top of 
the device and an LED to display the operation condi-
tions in the “special function” operating mode. 
 
The “Special Function” operating mode includes the fol-
lowing functions: 
 

  Connecting radio sensors with the function switching 

“ON/OFF” or scene 

  Activating/deactivating the time switch function 

  Clearing connections to radio sensors 

  Resetting the device to the supplied state 

 
 
 
 
 

Technical Specifications 

 

Frequency band 

  868 MHz (transmission is not susceptible to interfer-

ence; frequency band reserved for system and secu-
rity applications) 

 

Range of radio control 

  Approx. 100 m in clear area 

 

Power supply 

  230V power supply via terminals 2 (L1) and 3 (N) 

  Rated voltage: AC 230V, 50 Hz 

  Protection via 16A circuit-breaker, 

characteristic B or C required 

 

Control elements 

  1 pushbutton: to switch between different operation 

and commissioning conditions 

 

Display elements 

  1 red LED: to display the operation conditions and 

settings during commissioning 

 

Outputs

 

  Number: 2 (relay contacts) 

  Rated voltage: AC 230V 

  Rated current: 16A at cos phi = 1 

 

Connections 

  5 screw terminals for power supply and load supply; 

wire-stripping length approx. 7 … 8 mm 

  The following conductors or cross sections are per-

missible: 
- 0.5 to 4 mm

2

 single-wire 

- 0.5 to 2,5 mm

2

 finely stranded 

 

Mechanical specifications 

 Housing: 

plastic 

  Dimensions: device installation, 

42 x 32 x 274.5 mm (W x H x L) 

  Weight: approx. 200 g 

  Fire load: approx. 5500 kJ 

 

Electrical safety 

  Pollution degree (according to IEC 60664-1): 2 

  Protection (according to EN 60529): IP 20 

  Overvoltage category (according to IEC 60664- 1) III 

 Device 

complies 

with EN 60669-2-1 

 Relays 

with 

µ

 contact 

 
 

Содержание GAMMA wave GE 561/01

Страница 1: ...led on the top of the device and an LED to display the operation condi tions in the special function operating mode The Special Function operating mode includes the fol lowing functions Connecting radio sensors with the function switching ON OFF or scene Activating deactivating the time switch function Clearing connections to radio sensors Resetting the device to the supplied state Technical Speci...

Страница 2: ...ctural factors e g reinforced concrete or electric electronic sources of interference A distance of at least 1 m must be maintained be tween the transmitter and the relevant receivers Although the radio transmission occurs in the safe 868 MHz frequency band interference in the radio transmission cannot be ruled out The radio transmission used is not suitable for secu rity applications V DANGER The...

Страница 3: ...iver will be reduced and telegram losses may thereby occur 1 2 3 4 5 Kanal 1 L 1 N L 2 Kanal 2 C1 C2 C3 C4 Diagram C C1 Screw terminals C2 Wire fixing C3 Pushbutton C4 LED 1 2 L1 3 N 4 L2 5 Diagram D Terminal assignment Diagram D 1 Load output channel A 2 L1 Power supply L for actuator electronics and channel A 3 N Power supply N for actuator electronics 4 L2 Power supply L for channel B 5 Load ou...

Страница 4: ...utton F2 for the duration of up to 3 seconds switches the actuator to the special function channel A operating mode This is displayed by a slow flashing with approx 0 5 Hz once in 2 seconds of the LED F3 Special function for channel B A long actuation of the pushbutton F2 for the duration of 3 to 6 seconds switches the actuator to the special function channel B operating mode This is displayed by ...

Страница 5: ... B of the switch actua tor are deleted The device is in the supplied state If the pushbutton remains pushed for a maximum of 3 seconds or for 3 to 6 seconds after resetting to the sup plied state it will be directly switched to the special function channel A or special function channel B Time switch operation on period 1 to 60 minutes The two channels of the switch actuator wave can be operated re...

Страница 6: ...F3 begins to flash slowly once in 2 seconds with approx 0 5 Hz upon release of the pushbutton within 3 seconds or 1B Switch on special function channel B Action Long actuation of the pushbutton F2 for the duration of 3 to 6 seconds Display After 3 seconds the LED F3 flashes briefly approx 0 1 sec once After the release of the pushbutton within 3 to 6 seconds the LED shows a steady light 2 Select t...