Connect power supply and load circuit (Diagram C) 
-  The connections for the power supply and the load 

circuits are composed of screw terminals (C1). 

-  Insulate the conductors to be connected approx.  

7 … 8 mm, place in the terminals (C1) and screw in. 

-  The lead sheath is to be attached with the wire fixing 

(C2) to the housing of the installation device. 

 

Note:

 Conductors up to 1.5 mm

2

 single-wire can be 

looped directly to the terminal. It should be noted with 
looping that the maximum terminal current of 16 A must 
not be exceeded! 
With installation it should be noted that the outer conduc-
tor (L) and the neutral conductor (N) must not be trans-
posed, since otherwise the sensitivity of the radio re-
ceiver will be reduced and telegram losses may thereby 
occur. 
 

1

2

3

4

5

Kanal 1

L 1

N

L 2

Kanal 2

C1

C2

C3

C4

 

 

Diagram C 

 
C1 Screw 

terminals 

C2 Wire 

fixing 

C3 Pushbutton 
C4 LED 
 
 

1
2  L1
3  N
4  L2
5

 

 

Diagram D 

 
Terminal assignment (Diagram D) 
 
1   ––

  Load output channel A 

2   L1  Power supply (L) for actuator electronics and 

channel A 

3   N 

Power supply (N) for actuator electronics 

4   L2 

Power supply (L) for channel B 

5   ––

  Load output channel B 

 
 

Note:

 An outer conductor must always be connected to 

terminal 2 (L1) even if channel A is not used, since the 
actuator electronics are supplied with current via termi-
nals 2 and 3. 
 

A

E1

1

2  L1

3  N

4  L2

5

L1 L2 N

B

E3

E4

E5

E6

E2

 

Diagram E 

Connection example 
E1  Switch actuator wave GE 561/01 
E2 Actuator 

electronics 

E3  Switch channel A 
E4  Switch channel B 
E5  Power supply AC 230V, 50 Hz 
E6  Electric loads (e.g., lights) 
 
 

Location and Function of the Display and Operating 
Elements 

 
Diagram C 
C3  Pushbutton to switch over to the “special function” 

operating mode, to select the commissioning func-
tions and to connect the switch actuator via radio. 

C4  LED to display different settings and conditions in 

the “special function” operating mode during com-
missioning. 

 
 

Dimension Diagram 

 
Dimensions in mm 
 

 

 

 mounting holes  249 - 251

274,5

42

32

 

Содержание GAMMA wave GE 561/01

Страница 1: ...led on the top of the device and an LED to display the operation condi tions in the special function operating mode The Special Function operating mode includes the fol lowing functions Connecting radio sensors with the function switching ON OFF or scene Activating deactivating the time switch function Clearing connections to radio sensors Resetting the device to the supplied state Technical Speci...

Страница 2: ...ctural factors e g reinforced concrete or electric electronic sources of interference A distance of at least 1 m must be maintained be tween the transmitter and the relevant receivers Although the radio transmission occurs in the safe 868 MHz frequency band interference in the radio transmission cannot be ruled out The radio transmission used is not suitable for secu rity applications V DANGER The...

Страница 3: ...iver will be reduced and telegram losses may thereby occur 1 2 3 4 5 Kanal 1 L 1 N L 2 Kanal 2 C1 C2 C3 C4 Diagram C C1 Screw terminals C2 Wire fixing C3 Pushbutton C4 LED 1 2 L1 3 N 4 L2 5 Diagram D Terminal assignment Diagram D 1 Load output channel A 2 L1 Power supply L for actuator electronics and channel A 3 N Power supply N for actuator electronics 4 L2 Power supply L for channel B 5 Load ou...

Страница 4: ...utton F2 for the duration of up to 3 seconds switches the actuator to the special function channel A operating mode This is displayed by a slow flashing with approx 0 5 Hz once in 2 seconds of the LED F3 Special function for channel B A long actuation of the pushbutton F2 for the duration of 3 to 6 seconds switches the actuator to the special function channel B operating mode This is displayed by ...

Страница 5: ... B of the switch actua tor are deleted The device is in the supplied state If the pushbutton remains pushed for a maximum of 3 seconds or for 3 to 6 seconds after resetting to the sup plied state it will be directly switched to the special function channel A or special function channel B Time switch operation on period 1 to 60 minutes The two channels of the switch actuator wave can be operated re...

Страница 6: ...F3 begins to flash slowly once in 2 seconds with approx 0 5 Hz upon release of the pushbutton within 3 seconds or 1B Switch on special function channel B Action Long actuation of the pushbutton F2 for the duration of 3 to 6 seconds Display After 3 seconds the LED F3 flashes briefly approx 0 1 sec once After the release of the pushbutton within 3 to 6 seconds the LED shows a steady light 2 Select t...

Отзывы: