Commissioning
3.1 Connecting Power
SITRANS FUH1010 Quick Start
18
Operating Instructions (Compact), 12/2008, CQO:QSG010 Revision A
5.
Wire input power connector P8 for AC or DC power depending on power supply provided
as shown below. Insert wires into wire entry holes and secure by tightening wire clamp
screws (see figure below).
Note
Power Supply connector wires should be stripped AWG 12-18 stranded wire or solid
conductors.
Terminal Number
1010X-6SS2
1010X-6ZNS2
1010X-6ZPS2
1
Hot
Positive
Positive
2
Neutral
Negative (Gnd)
Negative (Gnd)
3
Ground
Ground
Ground
6.
Plug input power connector P8 into connector J8 and secure using two captive connector
mounting screws as indicated below.
7.
Secure power input cable with cable clamp to prevent wire breakage.
8.
Replace Rear Housing Cover and tighten setscrew.
9.
Connect the power cables to the appropriate power source previously selected from the
tables above and power up unit (100-250 VAC @ 50/60 Hz or 9-36 VDC).
Note
Loosen Wire Clamp Screw, insert stripped end of wire and then retighten.
+271(8*1'
*1'
3
$&
'&
3
①
Wire Clamp Screws
②
Connector Mounting Screws
③
Stripped Wire
Figure 3-1
Input Power Connector (P8) Wiring
Table 3- 1
Color Codes
HOT
NEU
GND
USA
BK
WH
GRN
EU
BR
BL
Y/GRN
Содержание FUH1010 IP65 NEMA 7 Compact
Страница 2: ......
Страница 14: ......
Страница 18: ......
Страница 36: ......
Страница 40: ......
Страница 46: ......
Страница 60: ......
Страница 64: ......
Страница 106: ......
Страница 110: ......
Страница 132: ......
Страница 152: ......
Страница 156: ......
Страница 178: ......
Страница 187: ......