Operation
Indicating and scrolling in lists
6
20 | 32
Building Technologies
009311_k_en_--
Fire Safety
2015-12-15
'Fault' and 'Intervention Concept' ('IC')
On consideration of 'Intervention Concept', events of the 'Fault' category can be
assigned their own sequence. This sequence may be configured differently and
depends on the 'Manned operation' / 'Unmanned operation' operation mode.
An exemplary sequence after a 'Fault', on consideration of the 'Intervention
Concept', is graphically represented in the following:
'Fault' has occurred
● 'Unmanned operation' operation mode
– Remote transmission for 'Faults' is activated
● 'Manned operation' operation mode
– The remote transmission for 'Faults' is activated unless the 'Fault' is
acknowledged within the delay t1.
1. Read the location of 'Fault' on the display.
2. Go to the location of 'Fault'.
3. Rectify 'Fault'.
See also
2
Faults / Troubleshooting [➙ 27]
6.3 Indicating and scrolling in lists
'Events' and conditions, starting from the ↑ floor repeater display's ↑ visibility, are
indicated in lists.
Generally the list with the 'Events' of the highest priority is automatically displayed
on the floor repeater display.
For example the alarm list is automatically displayed when 'Isolations', 'Faults'
and an 'ALARM' have occurred.
If a list contains several 'Events', you may scroll to the next list item by means of
the navigation buttons. The next 'Event' is highlighted.
When the 'ALARM' event list is open, the <More alarms> button assumes the
function of the button <▼>, changing to the next alarm event upon activation.
See also
2
Maximum number of events that can be displayed [➙ 14]