Operation
Procedure in case of Fault
6
19 | 32
Building Technologies
009311_k_en_--
Fire Safety
2015-12-15
Procedure in the event of alarm
Step
Action / Condition
Consequence / Status
1
Read top line on display
– 'Fire Brigade requested'
'ALARM' is transmitted to the fire brigade
– 'Fire Brigade in' 'mm:ss'
'ALARM' is transmitted to fire brigade in 'mm:ss'
Remaining time is shown as Countdown
– 'Call Fire Brigade !'
If:
Remote transmission switched off
Remote transmission blocked or defective
No remote transmission available
Fire brigade must be called by phone!
No automatic transmission to fire brigade
2
Read off fire location on display
3
Go to the fire location
4
Decide: MAJOR INCIDENT or ↑ minor
incident
Condition
MAJOR INCIDENT
↑ Minor incident
Fire brigade has been called
Save people
Guide the fire brigade to the fire
location
Fight the fire
Try to prevent fire brigade
deployment
'Fire Brigade in' 'mm:ss'
Countdown is running
Trigger 'Manual call point' immediately Try to prevent fire brigade
deployment
'Call Fire Brigade !'
No automatic transmission to
the fire brigade
Call the fire brigade on the phone!
6.2 Procedure in case of Fault
Step
Action
1
Press <Buzzer on/off> on the ↑ Person Machine Interface
2
Read off fault location on display
3
Go to the fault location
4
Eliminate the cause of the fault
A list of possible 'Faults' and how they are eliminated can be found in the chapter
'Faults / Troubleshooting'
If you cannot eliminate a 'Fault', please contact your service provider.