Safety

Standards and directives complied with

2

13 | 32

Building Technologies

009311_k_en_--

Fire Safety

2015-12-15

2.3 Standards and directives complied with

A list of the standards and directives complied with is available from your Siemens

contact.

2.3.1 CPR conformity and firmware version

In order to satisfy Ordinance No. 305/2011 (the Construction Products Regulation –

 CPR), the firmware of a newly installed fire detection installation must be current

market package version MP6 or higher.

NOTICE

Firmware version of a newly installed fire detection installation not updated
No CPR conformity
● Compare the firmware version of a newly installed fire detection installation

with the firmware version MP6.

● Update the firmware if necessary.

2.4 Release Notes

Limitations to the configuration or use of devices in a fire detection installation with

a particular firmware version are possible.

WARNING

Limited or non-existent fire detection
Personal injury and damage to property in the event of a fire.
● Read the 'Release Notes' before you plan and/or configure a fire detection

installation.

● Read the 'Release Notes' before you carry out a firmware update to a fire

detection installation.

NOTICE

Incorrect planning and/or configuration
Important standards and specifications are not satisfied.
Fire detection installation is not accepted for commissioning.
Additional expense resulting from necessary new planning and/or configuration.
● Read the 'Release Notes' before you plan and/or configure a fire detection

installation.

● Read the 'Release Notes' before you carry out a firmware update to a fire

detection installation.

Содержание FT2011

Страница 1: ...FT2011 Floor repeater display Operation Manual MP6 009311_k_en_ Building Technologies 2015 12 15 Control Products and Systems ...

Страница 2: ... communication thereof to others without express authorization are prohibited Offenders will be held liable for payment of damages All rights created by patent grant or registration of a utility model or design patent are reserved Issued by Siemens Switzerland Ltd Building Technologies Division International Headquarters Gubelstrasse 22 CH 6301 Zug Tel 41 41 724 2424 www siemens com buildingtechno...

Страница 3: ...13 2 3 1 CPR conformity and firmware version 13 2 4 Release Notes 13 3 Features 14 3 1 Maximum number of events that can be displayed 14 4 PMI 15 4 1 Buttons on the PMI 15 4 2 Display 16 4 3 LEDs 16 5 Service menu 17 6 Operation 18 6 1 ALARM Procedure 18 6 2 Procedure in case of Fault 19 6 3 Indicating and scrolling in lists 20 6 4 Open service menu Select menu item 21 7 Alarm verification concept...

Страница 4: ...Building Technologies 009311_k_en_ Fire Safety 2015 12 15 4 32 ...

Страница 5: ...igure the product at the place of installation according to customer specific requirements Check the product operability and release the product for use by the operator Searches for and corrects malfunctions Has obtained suitable specialist training for the function and for the products Has attended the training courses for commissioning personnel Maintenance personnel Carries out all maintenance ...

Страница 6: ...rmation for a behavior instruction Intermediate result of a behavior instruction End result of a behavior instruction Numbered lists and behavior instructions with an operation sequence X Reference to a page number Text Quotation reproduced identically Key Identification of keys Relation sign and for identification between steps in a sequence e g Menu bar Help Help topics Text Identification of a ...

Страница 7: ..._________________________________ __ ABCD 026 ABC 75 ABCDE CCC XXX YYY ZZZ 3 __________________________________ __ XXX YYY ZZZ 2 Table 1 Display representation in tables The table representation has the following key deviations from the original Font and representation proportional font not inverted No frame around selection 1 2 Applicable documents Sinteso document ID Title 008838 FC20xx FT2040 o...

Страница 8: ...sion or a country variant may for example be version d instead of a if the reference document is already this version The table below shows this document s revision history Version Edition date Brief description k 2015 12 15 Edition for MP6 IP6 Referenced documents updated j 2014 01 28 Chapter LEDs revised i 2013 11 14 Edition for MP5 IP5 h 2013 05 20 Change to date format according to ISO 8601 CP...

Страница 9: ...dangers the type of danger or possible consequences measures and prohibitions examples of which are shown in the following table General danger Explosive atmosphere Voltage electric shock Laser light Battery Heat Signal word The signal word classifies the danger as defined in the following table Signal word Danger level DANGER DANGER identifies a dangerous situation which will result directly in d...

Страница 10: ...is shown as follows WARNING Nature and origin of the danger Consequences if the danger occurs Measures prohibitions for danger avoidance How possible damage to property is presented Information about possible damage to property is shown as follows NOTICE Nature and origin of the danger Consequences if the danger occurs Measures prohibitions for danger avoidance ...

Страница 11: ...and supervision of a qualified electrician in accordance with the electrotechnical regulations Wherever possible disconnect products from the power supply when carrying out commissioning maintenance or repair work on them Lock volt free areas to prevent them being switched back on again by mistake Label the connection terminals with external external voltage using a DANGER External voltage sign Ro...

Страница 12: ...y be produced Before testing the remote transmission inform the corresponding alarm and fault signal receiving stations Modifications to the system design and the products Modifications to the system and to individual products may lead to faults malfunctioning and safety risks Written confirmation must be obtained from Siemens and the corresponding safety bodies for modifications or additions Modu...

Страница 13: ... Update the firmware if necessary 2 4 Release Notes Limitations to the configuration or use of devices in a fire detection installation with a particular firmware version are possible WARNING Limited or non existent fire detection Personal injury and damage to property in the event of a fire Read the Release Notes before you plan and or configure a fire detection installation Read the Release Note...

Страница 14: ... events is limited You will find details in the corresponding section 3 1 Maximum number of events that can be displayed The maximum number of events that can be displayed is limited and depends on the length of the event texts Assuming that the event texts are long the following maximum numbers of events apply to the corresponding displays Extended view 18 Standard view 37 Details view 20 Events ...

Страница 15: ...on buttons 7 LED System On 4 Silence buzzer button 4 1 Buttons on the PMI Navigation buttons The navigation buttons work in the same way as the arrow keys on a PC keyboard With the buttons and it is possible to scroll to the next entry in a list Silence buzzer Switches the buzzer off More alarms By pressing the More alarms button the display changes to the next alarm event In case of alarm this bu...

Страница 16: ... or green The LEDs can be configured according to customer specific requirements The LED colors can for example signal the following information Red ALARM Activations e g remote transmission alarm devices control function Yellow Fault Isolation Deactivation e g remote transmission alarm devices control function Green System is in operation Additional information on the conditions of the LEDs stead...

Страница 17: ...r calling up the menu and entering a password the following menu items are available Device information Shows detailed information on the device Buzzer on off Settings of the buzzer LED test Function test of the LED Key test Function test for the buttons of the PMI LCD test Function test of the display LCD contrast Setting of the display contrast in percent exit Closes the service menu See also 2 ...

Страница 18: ...5 6 Operation 6 1 ALARM Procedure If your fire detection system has no delayed alarm transmission function AVC the variant Fire Brigade in mm ss in Step 1 see Procedure in the event of alarm does not apply Figure 4 ALARM operation sequence 1 Read the top line 2 Read off the fire location 2 1 ...

Страница 19: ...he fire location 4 Decide MAJOR INCIDENT or minor incident Condition MAJOR INCIDENT Minor incident Fire brigade has been called Save people Guide the fire brigade to the fire location Fight the fire Try to prevent fire brigade deployment Fire Brigade in mm ss Countdown is running Trigger Manual call point immediately Try to prevent fire brigade deployment Call Fire Brigade No automatic transmissio...

Страница 20: ...ss the Fault is acknowledged within the delay t1 1 Read the location of Fault on the display 2 Go to the location of Fault 3 Rectify Fault See also 2 Faults Troubleshooting 27 6 3 Indicating and scrolling in lists Events and conditions starting from the floor repeater display s visibility are indicated in lists Generally the list with the Events of the highest priority is automatically displayed o...

Страница 21: ...u can only be opened when no Event is displayed Opening the service menu w No Event are displayed 1 Press More Alarms with Reset button pressed a The password dialog is shown 2 Enter the password and confirm a The service menu is open Select menu item In the service menu the highlighted menu item can be executed by pressing the More Alarms button or by opening the sub menu The buttons and highligh...

Страница 22: ...lse alarm or minor incident the intervention of the fire brigade can be avoided Information flow of ALARM and Pre ALARM D Detection tree AL Pre ALARM ALARM AVC Alarm verification concept GS Danger levels 1 Area The Area receives Pre ALARMS or ALARMS from Zones Alarm verification takes place at Area level Configuration for Pre ALARMS and ALARMS is not related within AVC The type of verification and...

Страница 23: ...ident or false alarm the operator may reset the ALARM and cancel alarming If the ALARM is not reset within the given time t2 Immediate global alarming is activated 7 3 Example of a verification process Alarm verification proceeds as follows An alarm event activates local alarming and starts the time t1 for attendance check Operating personnel acknowledge ALARM on the operating terminal prior to th...

Страница 24: ...on 2 Local alarming qx Not acknowledged 3 Manual call point or Alarm delay off on Station t2 Time t2 to investigate the source of alarm the fire location mx Unmanned operation operation mode t2 X Time t2 has expired m Manned operation operation mode r Reset on Station t1 Time t1 for attendance check rx Not reset t1 X Time t1 has expired GA Global alarming t2 t1 t2 X t1 X 1 mx m 2 q r qx rx GA 3 ...

Страница 25: ... the alarm devices can be configured differently for local and global alarming the alarm devices must be suitable for this Remote transmission The alarm message is transmitted to an intervention station In the case of local alarming this is usually the company fire brigade and for global alarm usually the state fire brigade A remote transmission device must be used to transmit alarm messages via t...

Страница 26: ... devices and the remote transmission can be separately configured for Alarm type only with automatic zones Pre ALARM ALARM Zone type only with ALARMS Manual alarm Automatic alarm Degraded fire alarm Operation mode Manned operation Unmanned operation Alarming type Local alarming only Delayed alarming Global alarming only ...

Страница 27: ...nsert Detector Detector defective Replace Detector with replacement detector CAUTION Any defective Detector must always be replaced by a Detector of the same type Manual call point Glass pane broken Replace glass pane Other damages Contact service provider Mains failure Mains failure in the public network No action required Emergency power supply is ensured by batteries during at minimum 12 hours ...

Страница 28: ...echnologies 009311_k_en_ Fire Safety 2015 12 15 9 Maintenance Please adhere to the local provisions No maintenance work is required Cleaning the PMI To clean the PMI use a wet cloth without any cleaning agents abrasives or solvents ...

Страница 29: ...orces e g the fire brigade are alerted Local alarming Local alarming equipment e g acoustic or optical is actuated in order to call up intervention personnel and to alert people of a possible fire hazard Minor incident Alarm situation which the operating personnel can handle themselves and does not therefore trigger global alarming PMI The arrangement of operating and display elements on a fire co...

Страница 30: ...ty 2015 12 15 Index A Alarm verification concept AVC 22 Example of verification process 23 AVC Alarm verification concept 22 Example of verification process 23 D Download center URL 8 L LEDs Colors 16 O Original language Source language 5 S Source language 5 ...

Страница 31: ...Index 31 32 Building Technologies 009311_k_en_ Fire Safety 2015 12 15 ...

Страница 32: ...ernational Headquarters Gubelstrasse 22 CH 6301 Zug 41 41 724 24 24 www siemens com buildingtechnologies Siemens Switzerland Ltd 2006 Technical specifications and availability subject to change without notice Document ID 009311_k_en_ Manual FS20 FS720 Edition 2015 12 15 ...

Отзывы: