Operation
Procedure in case of Fault
6
22 | 40
Building Technologies
009310_l_en_--
Fire Safety
2018-08-29
6.4 Procedure in case of Fault
Step
Action
1
Press <Buzzer on/off> on the ↑ Person Machine Interface
2
Read message/fault location on the display
3
Press <Acknowledge> on the Person Machine Interface
5
Go to the fault location
6
Eliminate the cause of the fault
A list of possible 'Faults' and how they are eliminated can be found in the chapter
'Faults / Troubleshooting'.
If you cannot eliminate a 'Fault', please contact your service provider.
'Fault' and 'Intervention Concept' ('IC')
On consideration of 'Intervention Concept', events of the 'Fault' category can be
assigned their own sequence. This sequence may be configured differently and
depends on the 'Manned operation' / 'Unmanned operation' operation mode.
An exemplary sequence after a 'Fault', on consideration of the 'Intervention
Concept', is graphically represented in the following:
'Fault' has occurred
● 'Unmanned operation' operation mode
– Remote transmission for 'Faults' is activated.
● 'Manned operation' operation mode
– The remote transmission for 'Faults' is activated unless the 'Fault' is
acknowledged within the delay t1.
Acknowledging 'Fault'
1. Press <Acknowledge> before the expiry of t1.
The local ↑ alarming equipment is silenced.
2. Read the location of 'Fault' on the display.
3. Go to the location of 'Fault'.
4. Rectify 'Fault'.
See also