Operation
ALARM Procedure
6
20 | 40
Building Technologies
009310_l_en_--
Fire Safety
2018-08-29
Procedure in the event of alarm
Step
Action / Condition
Consequence / Status
1
Press <Acknowledge> on the ↑ Person
Machine Interface
With 'AVC', countdown t2 for the examination of the
'ALARM' source starts
2
Read top line on display
– 'Fire Brigade requested'
'ALARM' is transmitted to the fire brigade
– 'Fire Brigade in' 'mm:ss'
'ALARM' is transmitted to fire brigade in 'mm:ss'
Remaining time is shown as Countdown
– 'Call Fire Brigade !'
If:
● Remote transmission switched off
● Remote transmission blocked or defective
● No remote transmission available
Fire brigade must be called by phone!
No automatic transmission to fire brigade
3
Read off fire location on display
4
Go to the fire location
5
Decide: MAJOR INCIDENT or ↑ minor incident
Condition
MAJOR INCIDENT
↑ Minor incident
Fire brigade has been called
Save people
Guide the fire brigade to the fire
location
Fight the fire
Try to prevent fire brigade
deployment
Press <Reset>
'Fire Brigade in' 'mm:ss'
Countdown is running
Trigger 'Manual call point' immediately
or
Press <Alarm delay off>
Press <Reset>
'Call Fire Brigade !'
No automatic transmission to
the fire brigade
Call the fire brigade on the phone!
Press <Reset>
To reset, the key switch must be used.
It may be necessary to air the room before resetting is possible.
Elements that cannot be reset can be switched off temporarily on the control
panel.