4.5.1 Alarm sounder with ES < 30
No.
Tone
Frequency pattern
Sweep from to
Pulse pattern
Adjustable sound levels (typ.
values in [dBA/1 m]
1
)
Norm
at 12 V
at 32 V
1
Continuous
970 Hz
97
87
80
100
91
81
'evacuate'
BS 5839 Part 1 1988
2
Intermittent
950 Hz
96
87
79
100
91
81
'alert'
BS 5839 Part 1 1988
3
Sweep-down
1,200 Hz 500 Hz
96
87
79
100
91
80
DIN tone
DIN 33404 Part 3
4
Slow-whoop
Sweep-up,
linear
500 Hz 1,200 Hz
97
88
81
101
92
82
NEN 2575
(Netherlands)
5
Pulse tone
500 Hz
94
85
77
97
88
77
Swedish Standard
SS 03 17 11, No. 1
'Imminent Danger'
6
Intermittent
500 Hz
93
84
75
96
87
75
Swedish Standard
SS 03 17 11, No. 3
'Important Message'
7
Continuous
500 Hz
94
85
78
97
88
78
Swedish Standard
SS 03 17 11, No. 4
'All clear'
8
Alternating
560 Hz
440 Hz
94
85
77
98
89
76
'French fire sound'
NF S 32-001 -1975
9
Intermittent
420 Hz
92
83
75
96
87
78
Australia 'Alert'
AS 2220-1978
10
Slow-whoop
Sweep-up,
linear
500 Hz 1,200 Hz
96
87
80
100
91
80
Australia 'Action'
AS 2220-1978
11
Intermittent
970 Hz
97
87
80
100
90
81
ISO 8201
US Temporal Tone LF
1
Details of sound level ±2 dBA
The sound level depends on the angle. See 'Technical data annex'
0
1 s
1 s
0
0
3.5 s
0.5 s
0
0.1 s
0.4 s
0
3.5 s
0.5 s
0