Specifications
Technical data
8
43 | 50
Building Technologies
008109_m_en_--
Fire Safety
2016-02-09
8 Specifications
8.1 Technical data
You will find information on approvals, CE marking, and the relevant EU directives
for this device (these devices) in the following document(s); see 'Applicable
documents' chapter:
Document 007026
Detector line
Operating voltage
DC 12…33 V
Operating current:
Standby
250 A
Sound activated
3.5 mA
Maximum current connection factor 15
Quiescent current connection factor 1
Address connection factor
1
Separator connector factor
1
Communication protocol
FDnet/C-NET
System compatibility
See 'List of compatibility'
Line separator
Line voltage:
Nominal
DC 32 V (= V
nom
)
Minimum
DC 12 V (= V
min
)
Maximum
DC 33 V (= V
max
)
Voltage at which the separator
opens:
Minimum
DC 7.5 V (= V
SO min
)
Maximum
DC 10.5 V (= V
SO max
)
Permanent current when switches
are closed
Max. 0.5 A (= I
C max
)
Switching current (e.g., in the event
of a short-circuit)
Max. 1 A (= I
S max
)
Leakage current when switches are
open
Max. 1 mA (= I
L max
)
Serial impedance when switches are
closed
Max. 0.5 (= Z
C max
)