In the device line, up to 30 of any compatible devices in
polarity  insensitive  mode  with  20  ohms  max  line
resistance  can  be  isolated between  two  modules  in
isolator mode in a Class A Style 6 wiring.
In the device line, up to 30 of any compatible devices in
polarity  insensitive  mode  with  20  ohms  max  line
resistance can be isolated behind one module in isolator
mode in a Class B Style 4 wiring.

HLIM  isolator  module  and  SBGA-34  sounder  base
cannot be used in the same loop with the modules in
isolator mode.

FCC Statement

WARNING!

Installation and usage of equipment not in accordance with instructions manual may
result in:

Radiation of radio frequency energy
Interference to radio communications

·

  Install and use equipment in accordance with installation instructions manual

·

  Read the following information

This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in
accordance with the instructions manual, may cause interference to radio communications.
It has been tested and found to comply with the limits for a Class A computing device pursuant to Part 15 of FCC
Rules, which are designed to provide reasonable protection against such interference when operated in a
commercial environment.
Operation of this equipment in a residential area is likely to cause interference in which case the user at his own
expense will be required to take whatever measures may be required to correct the interference.

Содержание FDOT421

Страница 1: ...smoke while pockets between them can contain a reduced level of smoke Take obstructions created by girders joists beams air conditioning ducts or architectural design into consideration when determining area protection Refer to the Initiating Devices chapter of NFPA Standard 72 for Location and Spacing requirements for specific types of construction e g beam suspended level sloped and peaked ceili...

Страница 2: ...he parameter setting Robust is changed to Duct which shall only be used in Duct applications When using this detector direct in air duct applications be sure the detector is set to the parameter Duct Alarm source 2 Heat only Fixed 135 F 57 C Rate of rise detection 15 F min 8 3 C at fixed 135 F 57 C WIRING The FDOT421 supports two operation modes polarity insensitive mode and isolator mode The Dete...

Страница 3: ...r is marked DO NOT PAINT This is intended to prohibit painting during routine maintenance of the occupancy which can affect proper operation of the detector Polarity insensitive wiring Figure 2 Isolator mode wiring Figure 3 Wire size maximum 14 AWG minimum 18 AWG Wire larger than 14 AWG can damage the connector TO INITIATING CIRCUIT OF SIEMENS COMPATIBLE CONTROL UNIT OPTIONAL REMOTE ALARM INDICATO...

Страница 4: ...the same loop with the modules in isolator mode FCC Statement WARNING Installation and usage of equipment not in accordance with instructions manual may result in Radiation of radio frequency energy Interference to radio communications Install and use equipment in accordance with installation instructions manual Read the following information This equipment generates uses and can radiate radio fre...