FUNCTIONAL TEST

Perform a functional (Go, No-Go) test by activating the
detector using the following test gases:

·

  Smoke Sabre, P/N SMOKESABRE-01-001

·

  Smoke Centurion (M8), P/N M8-001-024

·

  Solo A5 Smoke Detector Tester Gas

P/N SOLOA5 001

·

  Solo A10, P/N SOLO A10 / A10s

·

  Testifire 1001 / 2001, P/N TS3-001

·

  HSI PurCheck, P/N HO-30S

·

  HSI SmokeCheck™, P/N HO-25S

Follow the instruction on the gas canister label. This test
is  simply  used  to  ensure  that  smoke  can  enter  the
sensing chamber and alarm the control panel when the
detector  reaches  the  programmed  obscuration
(concentration) level.
The FDOT421 detectors can also be tested individually
using the DPU.
Refer to the DPU Manual, P/N 315-033260.

MAINTENANCE

The  control  unit  automatically  indicates  the  trouble
message  for  the  FDOT421  detector  whose  smoke
chamber changes to the level where the set sensitivity
cannot  be  maintained.  In  such  circumstances,  the
detector may require replacement.

CAUTION

Under  no  circumstances  is  the  detector  head  to  be
disassembled.
No repairs should be attempted.

DO NOT PAINT

The detector is marked DO NOT PAINT. This is intended
to  prohibit  painting  during  routine  maintenance  of  the
occupancy  which  can  affect  proper  operation  of  the
detector.

Polarity insensitive wiring:

Figure 2

Isolator mode wiring:

Figure 3

Wire size: maximum 14 AWG, minimum 18 AWG (Wire larger than 14 AWG can damage the connector)

TO INITIATING CIRCUIT
OF SIEMENS COMPATIBLE

CONTROL UNIT

OPTIONAL
REMOTE

ALARM
INDICATOR
MODELS

8727W / 8727C /
RL-HW / RL-HC

TO NEXT BASE

TO NEXT BASE

DO NOT USE AN
END OF LINE DEVICE

DETECTOR BASE
MODEL DB-11/DB-11E

LINE 1 *

LINE 2 *

5

6

1a

TB1

TB3

TB2

1b

5

6

1a

1b

** The relay contacts are shown after System reset, which represents the non-alarm condition.

* FDOT421 is a polarity insensitive detector. Line 1 and Line 2 can be either line of the loop.

5+

NO

C

NC

6-

RELAY 

**

CONTACTS

3A, 120 VAC
3A, 30 VDC

DO NOT USE AN
END OF LINE DEVICE

OPTIONAL

REMOTE
ALARM

INDICATOR
MODELS
8727W / 8727C /

RL-HW / RL-HC

TO NEXT BASE

TO NEXT BASE

DO NOT USE AN
END OF LINE DEVICE

DETECTOR BASE

MODEL DB-11/DB-11E

LINE 1

LINE 2

5

6

1a

TB1

TB3

TB2

1b

5

6

1a

1b

* The relay contacts are shown after System reset, which represents the non-alarm condition.

5+

NO

C

NC

6-

RELAY 

*

CONTACTS

3A, 120 VAC
3A, 30 VDC

DO NOT USE AN
END OF LINE DEVICE

+

+

To initiating circuit of
SIEMENS compatible control unit

Содержание FDOT421

Страница 1: ...smoke while pockets between them can contain a reduced level of smoke Take obstructions created by girders joists beams air conditioning ducts or architectural design into consideration when determining area protection Refer to the Initiating Devices chapter of NFPA Standard 72 for Location and Spacing requirements for specific types of construction e g beam suspended level sloped and peaked ceili...

Страница 2: ...he parameter setting Robust is changed to Duct which shall only be used in Duct applications When using this detector direct in air duct applications be sure the detector is set to the parameter Duct Alarm source 2 Heat only Fixed 135 F 57 C Rate of rise detection 15 F min 8 3 C at fixed 135 F 57 C WIRING The FDOT421 supports two operation modes polarity insensitive mode and isolator mode The Dete...

Страница 3: ...r is marked DO NOT PAINT This is intended to prohibit painting during routine maintenance of the occupancy which can affect proper operation of the detector Polarity insensitive wiring Figure 2 Isolator mode wiring Figure 3 Wire size maximum 14 AWG minimum 18 AWG Wire larger than 14 AWG can damage the connector TO INITIATING CIRCUIT OF SIEMENS COMPATIBLE CONTROL UNIT OPTIONAL REMOTE ALARM INDICATO...

Страница 4: ...the same loop with the modules in isolator mode FCC Statement WARNING Installation and usage of equipment not in accordance with instructions manual may result in Radiation of radio frequency energy Interference to radio communications Install and use equipment in accordance with installation instructions manual Read the following information This equipment generates uses and can radiate radio fre...

Отзывы: