Commissioning
34
Building Technologies
009865_b_en_--.doc
Fire Safety & Security Systems
11.2007
8.3
Register the radio detector at the radio gateway
Radio detectors can be registered on a radio gateway newly put in operation, or
they can be added to the existing configuration of a radio cell.
In either case the button in the radio gateway must be briefly pressed to either
change into configuration mode, either from the completed 'scan mode for the
basis channel', or from normal operation.
The configuration can be supported by the RadioSpy.
As an alternative to the button, it is possible to activate the reed contact.
Prerequisites:
z
The detector line FDnet is switched off.
z
The radio gateway is in configuration mode.
–
LEDs green/red are alternatingly flashing rapidly.
z
Number of registered radio detectors on the radio gateway < 30.
z
The radio detector is in delivery condition.
If the radio detector is not in delivery condition, first put it in that condition as described in the chapter
'Resetting the DOW1171 in delivery condition' or 'Resetting the SMF6120 in delivery condition'.
Procedure:
1.
Insert batteries in the radio detector and with the SMF6120 additionally press the
alarm button.
2.
Screw the DOW1171 into the base, or screw the
manual call point SMF121 into the radio base SMF6120 and actuate the
resetting slider for the alarm button.
Î
The radio detector is automatically registered at the radio gateway.
–
Successful registration: green LED on the radio gateway flashes rapidly for
5 seconds
–
Registration failed: red LED on the radio gateway flashes rapidly and
permanently
Î
The radio gateway automatically changes into configuration mode again.
Î
LEDs green/red are alternatingly flashing rapidly.
After the registration of the radio detector at the radio gateway, the status indicator
(LED) of the radio detector indicates the field strength for 2 minutes as follows:
Flashing sequence / s (second)
Field strength
4x/s high
3x/s medium
2x/s low
1x/s very
low
Note the serial number or registration requence and location of the radio detector.
Acceptable connection qualities with the radio gateway are exclusively those field
strengths indicated with a flashing sequence of 3x/s or 4x/s.