Function
23
Building Technologies
009865_b_en_--.doc
Fire Safety & Security Systems
11.2007
Operating
mode
LEDs red
H1, H4
LEDs green
H1, H2
LED yellow
H3
Meaning
Normal
operation
off
off
off
Normal, intended operation
flashing twice
off
off
No or insignificant battery voltage
Startup mode
off rapidly
flashing
for 10 s
off
The radio gateway can be reset in the
delivery status (the internal configuration is
deleted)
shortly flashing
1x
off
off
The button has been briefly pushed, or the
reed contact has been briefly acutated with a
magnet
off shortly
flashing
1x
off
Button is released after it has been held
down for longer
slowly flashing slowly flashing off
Channel search
off
slowly flashing off
Channel found
slowly flashing off
off
No free channel found
rapidly flashing rapidly flashing off
Registration of another radio detector on the
gateway
off rapidly
flashing
for 3 s
off
Radio detector has been registered on the
gateway
rapidly flashing off
off
The radio detector could not be registered on
the gateway (30 radio detectors have already
been registered)
off
off
slowly flashing The radio gateway is ready for the logging-off
of a radio detector
off
slowly flashing slowly flashing A radio detector has been recognized for
logging-off
(Note: The radio detector can be logged off
with the button)
Configuration
mode
rapidly flashing off
rapidly flashing Several radio detectors have been
recognized for logging-off
(Note: RadioSpy must be used to log off radio
detectors)
Tab. 1
Status of the radio gateway
Legend
LEDs:
slowly flashing
1x / second
rapidly flashing
4x / seconds
flashing twice
1x double / second
shortly flashing 1x
approx. 0.3 seconds
Button: press
shortly <1…2
seconds
keep pressed
>3 seconds
see also:
Î
8.6 Resetting the radio gateway in delivery condition, Page 38