Diagnostics
Press "Conn. Test" to test the KNX PL-Link connection.
A popup window shows the progress of the connection test:
Reset to factory
setting
STOP
Note! This operation resets all user preference data and
configuration settings to factory default.
This operation is irreversible.
Press "Fact. Reset". The device is locked and reboots within 10 seconds. The
room automation station deletes it from its device list. During this time, it is
safe to remove the device from the network.
If the room operator unit is not unplugged, it acts like a newly inserted device
requiring again automated or manual configuration.
Commissioning (plug & play)
When only one room operator unit is connected to the KNX PL-Link bus, the unit
automatically establishes communications with the room automation station, from
where the functions are downloaded to the room operator unit (plug & play).
The following routine is executed:
Step
Function
Description
1
Splash screen
The unique serial number of the device is displayed below the company
logo.
2
Busy
During configuration, 6 animated dots appear in the center of the screen
to indicate the device is busy.
This step is skipped if the device is already configured.
Note: The configuration file can be downloaded any time; as a result,
these dots are displayed every time the room automation station
initializes download.
7 / 14
Siemens
QMX3... Freely configurable flush-mounted room operator unit for KNX PL-Link
CM2N1601en_04
Building Technologies
2016-03-24