background image

  

A list item provides status information: 

   

 

Tick

: Indicates the current selection from the room automation station. A change 

from hourglass to tick indicates that the automation station has confirmed the 
modifications the user just made. 

 

Hourglass

: Indicates the progress of the selected activity. 

 

Lock

: Indicates locked entries that cannot be selected / enabled. 

 

Floppy disk

: Is only used in scene saving, and will be displayed for 1 second, 

then go back to "Tick". 

 

Maintenance 

The device can be cleaned with off-the shelf, solvent-free cleaning agents.  
Do not use mechanical aids (rough sponge or similar materials) – only a soft, damp 
cloth. 
Dismounting: see page 5. 
 

Technical data 

Supply voltage 

Operating voltage range 

KNX PL-Link DC 21...30 V 

 

The room operator unit receives its power from the connected room automation station 
via the KNX PL-Link interface 

 

Power consumption  
(from room automation station) 

Max.10 mA at DC 24 V 

Series A: Max.12.5 mA at DC 24 V 

Operating data 

Temperature sensor 

 

 

Measuring element 

NTC resistance sensor 

 

Measuring range 

0...50 °C 

 

Measuring accuracy (5 …  30 °C) 

±

0.61 K 

 

Measuring accuracy (25 °C) 

±

0.35 K 

Display 

Type 

Dot matrix LCD, resolution 96 x 128 

 

Information displayed depends on the 
application in the PXC3... room automation 
station 

 

Room temperature 

 

Setpoint adjustment 

 

Control mode 

 

Manually selected fan speed 

 

Control sequence 

 

Scenes 

 

etc. 

Ports/interfaces 

Type of port between room automation station 
and room operator unit 

KNX PL-Link 

 

Baud rate 

9.6 kbps 

 

Standard KNX plug 

Wire diameter0.8 mm, max. 1.0 mm 
(solid conductors only) 

 

Cable type 

Solid conductors 2-core, twisted pair 

 

Single cable length (from room automation 
station to room operator unit) 

<1000 m 

 

Cables must comply with KNX specifications, see TRA Installation manual, CM111043 

Housing protection  

Protection standard as per EN 60529 

IP 30 

Protection class 

Insulation protection class 

III 

 
 
 
 

Status information 

STOP

  

Note! 

10 / 14 

Siemens 

QMX3...   Freely configurable flush-mounted room operator unit for KNX PL-Link 

CM2N1601en_04 

Building Technologies 

 

2016-03-24 

Содержание Desigo TRA QMX3.P36F

Страница 1: ...s as part of Total Room Automation Energy efficiency function Green Leaf Room temperature measurement Display of room temperature control mode scenes etc LCD Backlit display white or blue selection KNX PL Link interface to the room automation station with plug play functionality Can be combined with different standard and design bezels CM2N1601en_04 2016 03 24 Building Technologies ...

Страница 2: ...ations Supported bezel programs Siemens DELTA DELTA line DELTA miro and DELTA vita For the DELTA style and DELTA profil series an adapter frame for 55mm x 55mm inserts is required Berker B 1 B 7 Gira Standard 55 E2 Event Esprit Jung A500 AS500 stainless steel LS990 aluminum Merten System M Feller EDIZIOdue PRESTIGE Adapter frame for 55mm x 55mm devices is required Bezels from various other manufac...

Страница 3: ... QMX3 P36G Bezels from various other manufacturers can also be used suitability to be clarified in advance The operator unit D incorporates the room temperature sensor element keys LCD panel KNX PL Link plug tool plug and spring clamps to hold the operator unit in the base plate Disposal The device is considered an electronics device for disposal in terms of European Directive 2012 19 EU and may n...

Страница 4: ...isplay and stick it on the floor plan to prepare commissioning for several room operator units per room automation station The same barcode label with unique identifier is available on the device Furthermore the unique identifier HEX number is displayed on screen when starting the device Mounting and installation The room operator unit is suitable for flush mounting Recommended height 1 50 m above...

Страница 5: ...d cause faulty temperature readings by the internal sensor Mounting instructions are printed inside the device package and are also on the plastic bag The operator unit may need to be dismounted from the base plate to exchange the operator unit 1 Hold bezel with one hand 2 Pull operator unit with the other hand Mounting Dismounting 5 14 Siemens QMX3 Freely configurable flush mounted room operator ...

Страница 6: ...commissioning All commissioning work is done via the PXC3 room automation station using the SSA DNT or the ABT The ABT is never connected directly to a room operator unit When more than one QXM3 P36 room operator unit is on the same trunk of the KNX PL Link bus manually commission is done as follows 1 Connect the SSA DNT or the ABT to the room automation station and activate the online commissioni...

Страница 7: ...hen only one room operator unit is connected to the KNX PL Link bus the unit automatically establishes communications with the room automation station from where the functions are downloaded to the room operator unit plug play The following routine is executed Step Function Description 1 Splash screen The unique serial number of the device is displayed below the company logo 2 Busy During configur...

Страница 8: ...only data point information or operable data point information can be displayed With a multi page navigation driven page set the information usually is laid out in the following format Line 1 Title read only data point information Line 2 Information Operable data point information display or setpoint Temperature air quality fan speed etc Line 3 Read only operable data point information Line 4 Info...

Страница 9: ...right key resets the application to energy efficient parameter values Save a changed scene by long pressing the key approx 3 sec 1 2 3 4 5 6 7 8 Notes A scene can only be saved if Scene Teaching is enabled in the application The key event to save a scene can be freely engineered In the default page set it is set to long press key 6 the keys are numbered left top to bottom and then right top to bot...

Страница 10: ...V Series A Max 12 5 mA at DC 24 V Operating data Temperature sensor Measuring element NTC resistance sensor Measuring range 0 50 C Measuring accuracy 5 30 C 0 61 K Measuring accuracy 25 C 0 35 K Display Type Dot matrix LCD resolution 96 x 128 Information displayed depends on the application in the PXC3 room automation station Room temperature Setpoint adjustment Control mode Manually selected fan ...

Страница 11: ...y CM2T1601en_C1 The product environmental declaration CM2E1601 contains data on environmentally compatible product design and assessments RoHS compliance materials composition packaging environmental benefit disposal Color Front housing Titanium white similar to RAL9010 Weight QMX3 P36F QMX3 P36G Operator unit 50 g 50 g Bezel base plate 32 g 63 g Packaging 44 g 54 g Total 126 g 167 g The documents...

Страница 12: ...7 Ident pin 8 GND OCI 702 PL Link Ethernet MS TP Connect the ABT to load the application in the room automation station or for service purposes Directly to the room automation station To the room unit using the tool cable and the OCI702 service interface see data sheet A6V10438951 Note Remove the operator unit from the base plate to connect the tool cable KNX PL Link plug STOP Note Tool plug 2 5 m...

Страница 13: ...DELTA line square Base plate square Bezel similar to DELTA azio rectangular Base plate rectangular 13 14 Siemens QMX3 Freely configurable flush mounted room operator unit for KNX PL Link CM2N1601en_04 Building Technologies 2016 03 24 ...

Страница 14: ... 2016 Siemens Switzerland Ltd Subject to change 14 14 Siemens QMX3 Freely configurable flush mounted room operator unit for KNX PL Link CM2N1601en_04 Building Technologies 2016 03 24 ...

Отзывы: