Examples of connection diagrams for universal inputs/outputs
Digital inputs
Ux
Ux
S1
S2
Feedback contact (NO)
Feedback contact (NC)
Count inputs:
Counter inputs, that count faster than 1 Hz and are laid with more than 10 meters using analog inputs in
the same cable duct, must be shielded.
Analog inputs
Ux
Ux
Ux
Ux
Ux
M
B
V
V
V
Ux
+
V+
+
+
+
B1
B2
B3
B4
B5
B6
Temperature sensor LG-Ni 1000
Temperature sensor, general
Resistance transmitter
Active sensor powered by the automation station
Active sensor with external power
Do NOT ground external power (ground loops)
Active sensors 0 ... 20 mA or 4 ... 20 mA (2-wire)
On U1, U2, U7, U8 only
Analog outputs
Ux
Ux
V
Ux
+
V +
V +
Y1
Y2
Y3
Device with input DC 0...10 V
General device with control input DC 0...10 V,
Powered by the automation station
General device with control input DC 0...10 V,
Do NOT ground external power (ground loops)