21/34
Siemens Building Technologies
PXM10 operator unit
CM110397en
Siemens Building Automation
31.08.2004
Notes
Note that for each object, only the current alarm, i.e. the last
alarm received, is displayed.
Acknowledged alarms and reset alarms are removed from
the PXM10 display.
Exception
Acknowledged extended alarms (which require a reset)
continue to be displayed in the alarm list until they are reset.
5.3 Acknowledging
alarms
Step Procedure
1
Highlight the required alarm in the alarm list (Figure 5-3).
The "bell" symbol shows the status of the alarm (see the
symbol in Section 2.3.3:
2
Acknowledge the next alarm.
Figure 5-7 Prompt for acknowledgement
Use the push-dial to select
No
or
Yes
and
acknowledge with OK.
The alarm LED will stop flashing and switch off. The
bell symbol is marked with a tick, representing
"acknowledged".
With extended alarms, which require a reset once
the fault has been cleared, the alarm LED stays on
(see Section 5.4).
3
Acknowledge the next alarm
or
Press Esc to close the alarm list.
Basic alarms disappear when the fault has been cleared:
they do not require acknowledgement.
Note