background image

 

2/34 

Siemens Building Technologies 

PXM10 operator unit 

CM110397en 

Building Automation 

 

31.08.2004 

 

Содержание DESIGO PX

Страница 1: ...s DESIGO PX PXM10 operator unit User s guide Version 2 3 CM110397en 31 08 2004 Siemens Building Technologies Building Automation ...

Страница 2: ...2 34 Siemens Building Technologies PXM10 operator unit CM110397en Building Automation 31 08 2004 ...

Страница 3: ...otes 6 2 Display and control elements 7 2 1 Layout 7 2 2 Push dial and buttons 8 2 2 1 Push dial 8 2 2 2 Esc button 8 2 2 3 Info button 9 2 2 4 Alarm button with alarm LED 9 2 3 Display panel 10 2 3 1 Menu line 11 2 3 2 Working area 11 2 3 3 Symbols 13 3 Commissioning the PXM10 14 3 1 Settings on the device 15 4 Reading and editing values 17 4 1 Example Setting a setpoint 17 5 Alarms and events 19...

Страница 4: ...110397en Building Automation Contents 31 08 2004 5 4 Resetting extended alarms 22 6 Scheduler 23 6 1 Day profile 23 6 1 1 Editing an existing profile 24 6 1 2 Adding a new entry 25 6 2 Special periods 26 6 2 1 Others 28 6 2 2 Adding a new entry 29 7 Index 31 ...

Страница 5: ...c configuration and use of the PXM10 operator unit As there may be significant differences between one plant and another and between one object and another it follows that it is not possible to provide a description which is generally applicable to every individual case The question of exactly which objects are integrated with which values in a plant is determined in the engineering phase accordin...

Страница 6: ...using The Acknowledge function OK is integrated into the push dial The Info and Esc buttons are labeled accordingly on the housing The Alarm button is not named on the housing but can be identified by the alarm symbol Press the Info button or more briefly Confirm with OK 1 3 3 Notes STOP Caution The symbol shown here acts as a warning in cases where an action may result in permanent loss of data I...

Страница 7: ...rator unit CM110397en Siemens Building Automation 31 08 2004 2 Display and control elements 2 1 Layout PXM10 INFO ESC OK 9230Z01 1 2 3 4 5 Figure 2 1 Housing Key 1 Info button 2 Display panel 3 Push dial 4 Alarm button with alarm LED 5 Esc button ...

Страница 8: ...an move from top to bottom of the text field and set or modify setpoints By pushing the dial you can navigate to the next level down and acknowledge a selected option or input this function is equivalent to selecting OK 2 2 2 Esc button Figure 2 3 Esc button Pressing the Esc button lets you abandon a process you have already started e g editing a value navigate to the next higher level or close a ...

Страница 9: ...again 2 2 4 Alarm button with alarm LED Figure 2 5 Alarm button with alarm LED The alarm LED lights up or flashes when an alarm or event is tripped in the system The alarm button takes you straight to the alarm list Alarm LED Sym bols Event Flashing Pending alarm unacknowledged pop up window and alarm list Incoming event pop up window only Steady light Pending alarm acknowledged and extended alarm...

Страница 10: ...s or other information Figure 2 7 shows the layout of the display The areas of the display and the symbols used are described in the next section The push dial and buttons used for navigation and editing are adjacent to the display panel set into the housing itself These buttons are described in Section 2 2 Menu line Working area with four lines of text one of which is highlighted Figure 2 7 Layou...

Страница 11: ...t from the rest of the display with a horizontal line Under Scheduler Special period you will see the entry Others which as a submenu is also underlined Figure 2 9 Submenu 2 3 2 Working area Figure 2 10 Working area Below the menu line is the working area which consists of a maximum of four alphanumeric lines of text Graphs are only displayed in the Scheduler menu If there are more lines than can ...

Страница 12: ...of which is highlighted If a line of text is outlined this indicates that you are at the lowest level and you can only read but not edit the value on this line Use the Esc button to navigate back to the next higher level Figure 2 12 Outlined text at the lowest level A pop up is a dialog box used to display an alarm or an event The alarm button provides direct access to the list of pending alarms F...

Страница 13: ...ntries or have a different meaning depending on the context Symbol Description Favorite objects These are defined at the engineering stage Pop up window Alarm or event Uncleared alarm neither acknowledged nor reset Uncleared but acknowledged alarm Alarm cleared but not acknowledged Alarm list Alarm cleared acknowledged but not reset Info window Info symbol Override Manually overwritten forced valu...

Страница 14: ...rately Step Action 1 Mount the PXM10 on the housing of the modular automation station or Connect the PXM10 to the compact or modular automation station with a PXA C1 cable 2 After a few seconds the display will light up and the opening screen will appear The PXM10 is now ready for operation Figure 3 1 Opening screen 3 Either open the plant data with OK or Press the alarm button to go directly to t...

Страница 15: ...enabled by operating any of the operator controls There is no need to log out Wait 30 seconds before reconnecting 3 1 Settings on the device Figure 3 2 Display showing plant data Step Procedure 1 Press OK to open the Settings menu Figure 3 3 Individual entries 2 Set individual values by rotating the dial and acknowledge the settings with OK You can also use OK to move from one input field to the n...

Страница 16: ...st value has been acknowledged the plant data screen is displayed automatically Contrast 100 High 0 Low Default 50 Time Digital display format hh mm Date Digital display format dd mm yy Event pop up Active inactive View Favorites Both Both lets you display both the Favorite objects and all the objects in the Standard user view ...

Страница 17: ...values you can edit and which you can only read Figure 4 1 Highlighted values can be edited Figure 4 2 Outlined values are read only Step Procedure 1 Navigate to the required setpoint the relevant line is highlighted 2 Select setpoint with OK 3 A dialog box opens in which you can set the value Figure 4 3 Setting a manual setpoint with one input field only Figure 4 4 Setting the time with two input...

Страница 18: ...ate the dial to set the required value in the input field Acknowledge with OK If a value is made up of two or more input fields the input focus will then switch to the next field 5 Confirm with OK or press Esc to cancel Press the Esc button to return automatically to the Setpoints screen Figure 4 2 Note ...

Страница 19: ...e notified accordingly in a pop up window Figure 5 1 If the PXM10 is only switched on after the occurrence of the alarm or event there will be no pop up window These alarms do however appear in the alarm list If you want to be notified of events in a pop up window you can activate this option under Settings Event popup Figure 5 1 Settings screen Figure 5 2 Activate event pop up window A pop up win...

Страница 20: ...ng the alarm 5 2 Displaying the alarm list Figure 5 5 The Alarms menu alarm list The alarm LED lights up and flashes Step Procedure 1 Display the alarm list either by use of the alarm button or by selecting the Alarms option Figure 5 6 Plant data screen 2 The alarm list opens Unacknowledged alarms and alarms that have been acknowledged but not yet reset are displayed here Each line contains the ob...

Страница 21: ...ight the required alarm in the alarm list Figure 5 3 The bell symbol shows the status of the alarm see the symbol in Section 2 3 3 2 Acknowledge the next alarm Figure 5 7 Prompt for acknowledgement Use the push dial to select No or Yes and acknowledge with OK The alarm LED will stop flashing and switch off The bell symbol is marked with a tick representing acknowledged With extended alarms which r...

Страница 22: ...et after the fault has been cleared Step Procedure 1 Navigate to the Alarms option Figure 5 4 2 Confirm with OK The alarm list opens Figure 5 3 3 Highlight the required alarm and confirm with OK 4 Clear the fault 5 Open the alarm list again 6 Select the required alarm and confirm with OK Figure 5 8 Resetting an alarm 7 Use the push dial to select No or Yes 8 Confirm with OK to reset the alarm 9 Th...

Страница 23: ... define switching operations to be repeated week after week In the Special period menu you define individual days which deviate from those defined in the day profile The names and locations of these time schedules are defined on a plant specific basis The following illustrations are examples only 6 1 Day profile In the Day profile you can define separate switching periods for each day of the week ...

Страница 24: ... 2004 6 1 1 Editing an existing profile Step Procedure 1 Highlight the Day Profile option and click OK to open it Figure 6 2 2 In the Day profile menu highlight the required day and click OK to open it Figure 6 3 A screen appears with a graph representing the day profile Figure 6 4 Day profile ...

Страница 25: ...e 6 5 Input fields for the day profile 4 Rotate the dial to set the required time and switch status Move to the next input field by pressing OK in each case 5 Finally confirm the inputs with OK 6 1 2 Adding a new entry Step Procedure 1 Highlight the Day Profile option and click OK to open it Figure 6 6 2 Highlight the required day and open it with OK Figure 6 7 ...

Страница 26: ...le Figure 6 8 3 Rotate the push dial until the cursor marks New entry and then define the new switching operation Figure 6 9 6 2 Special periods The Special period option is used to define individual days which deviate from those defined in the Day profile Step Procedure 1 Highlight the Special period option and open it with OK Figure 6 10 Special period ...

Страница 27: ...ilding Automation 31 08 2004 2 A window opens containing the following options New entry Define a new special period Others Edit an existing special period Figure 6 11 Special period screen 3 Continue as described in Section 6 2 1 Others or as in Section 6 2 1 Adding a new entry ...

Страница 28: ...04 6 2 1 Others Step Procedure 1 Open the required entry and confirm with OK Figure6 12 Existing entry under Others 2 Edit the individual values as required and confirm with OK Figure 6 13 Individual entries The date type and priority should be modified only by a fully trained person STOP Caution ...

Страница 29: ...set the required values Move to the next input field by pressing OK in each case The profiles are defined individually at the engineering stage The date type and priority should be defined only by a fully trained person 4 Confirm inputs with OK and use the Esc button to back out again You can use wildcards when entering the date type week day and the date Each wildcard represents any value in the ...

Страница 30: ... 2004 appear in the display panel in the form of the symbol shown to the left A new special period is to be defined which is to take effect on New Year s Day i e on 1 st January of every year The calendar year values change annually You should therefore enter the date as follows 01 01 Example ...

Страница 31: ...playing 20 Alarm pop up 19 Alarms Acknowledge 21 Reset 22 Alarms 19 Buttons Esc 8 Printing convention 6 Commissioning 14 Contrast 16 Day profile 23 Edit 24 New entry 25 Display 10 Graphs 13 Pop up 12 Working area 11 Display panel 10 Esc button 6 8 Event Enable pop up 16 Popup 19 Events 19 Graphs 13 Housing 7 Info button 9 Interruption 15 Keys Esc 8 LED 9 Logout 15 Menu line 11 ...

Страница 32: ...4 Pop up 12 Delete 20 Pop up window 19 Printing conventions 6 Redaing and editing values 17 Schedule Special period 26 Scheduler 23 Setting the date 16 Setting the object view 16 Setting the time 16 Settings 15 Special period 26 New entry 29 Others 28 Symbol Alarm 13 Favorite objects 13 Forced value 13 Info window 13 Pop up window 13 Wildcard 13 Wildcards 29 ...

Страница 33: ...33 34 Siemens Building Technologies PXM10 operator unit CM110397en Siemens Building Automation 31 08 2004 ...

Страница 34: ... CM110397en Building Automation 31 08 2004 Siemens Building Technologies Ltd Building Automation Gubelstrasse 22 CH 6301 Zug SWITZERLAND Tel 41 41 724 24 24 Fax 41 41 724 35 22 www sbt siemens com 2004 Siemens Building Technologies Ltd Subject to alteration ...

Отзывы: