background image

Figure 3  Wiring Diagram for DB-11/-11E using HFP-11 and HFPT-11 Detectors

Model DB-11/-11E

(P/N 500-094151/500-094151E)

Siemens Building Technologies, Inc.

8 Fernwood Road

Florham Park, New Jersey  07932

Siemens Building Technologies, Ltd.

2 Kenview Boulevard

Brampton, Ontario, Canada  L6T 5E4

Figure 2  Wiring Diagram for DB-11/-11E using FP-11, FPT-11, FS-DP, FS-DPT, and FS-DT Detectors

1a

6

-

-

-

-

-

-

-

+

+

+ +

+ +

+

TO INITIATING
CIRCUIT OF
SBT, INC.
COMPATIBLE
CONTROL UNIT

OPTIONAL
REMOTE
ALARM
INDICATOR
MODELS
RLI-1 / RLI-2

TO NEXT BASE

TO NEXT BASE

DO NOT
USE AN
END OF
LINE
DEVICE

DB-11/-11E (NO REMOTE DEVICE)

5

6

1a

1b

5

6

1a

1b

RELAY*
CONTACTS
3A, 120 VAC
3A, 30 VDC

DB-11XRS (REMOTE RELAY BASE)

*The relay contacts are shown in the Non-Alarm/System Reset condition.

5+

NO

C

NC

6–

5+

NO

C

NC

6–

DO NOT
USE AN
END OF
LINE
DEVICE

TO INITIATING
CIRCUIT OF
SBT, INC.
COMPATIBLE
CONTROL UNIT

OPTIONAL
REMOTE
ALARM
INDICATOR
MODELS
RL-HW / RL-HC

TO NEXT BASE

TO NEXT BASE

DO NOT
USE AN
END OF
LINE
DEVICE

DB-11/-11E (NO REMOTE DEVICE)

LINE 1**

LINE 2**

TB1

TB3

TB2

5

6

1a

1b

5

6

1a

1b

RELAY*
CONTACTS
3A, 120 VAC
3A, 30 VDC

DB-HR (REMOTE RELAY BASE)

*The relay contacts are shown in the Non-Alarm/System Reset condition.

**HFP-11/HFPT-11 is a polarity insensitive detector. Line 1 and Line 2 can be either line of the loop.

5+

NO

C

NC

6–

5+

NO

C

NC

6–

DO NOT
USE AN
END OF
LINE
DEVICE

Figure 1  Wiring Diagram for DB-11/-11E using PE-11, PE-11T, and DT-11 Detectors

CAUTION:
1. Do not use looped wire under base terminal 5. Break wire

run to provide supervision of connection.

2. When a remote relay is used to control a critical system

function, the relay and its associated detector and optional

module(s) must be the ONLY devices on the initiating circuit.

Installation/Wiring Instructions

MODEL DB-11/-11E DETECTOR BASE

Fire Safety

1b

6

5

END OF LINE DEVICE

(NOTE POLARITY

WHEN APPLICABLE)

1a

1b

1b

5

5

6

+

-

+

-

(SEE CAUTION 1)

MULTIPLE REMOTE DEVICES

If remote devices are supported by the initiating circuit, e

ach detector/base may

have up to 2 remote devices with the following configurations and restrictions only:

Remote

Device 1

RR-11
RR-11

RLC-11, RLW-11
RLC-11, RLW-11

Remote

Device 2

RLC-11, RLW-11

RSAC-11, RSAW-11
RSAC-11, RSAW-11

RLC-11, RLW-11

Restrictions

See Caution 2
See Caution 2
Wire from base to
RSAC-11/RSAW-11 to RL-11

SEE REMOTE DEVICE INSTRUCTIONS FOR WIRING DETAILS:

DEVICE

RR-11
RLC-11, RLW-11
RSAC-11, RSAW-11

INSTALLATION

INSTRUCTIONS

P/N 315-094924
P/N 315-094925
P/N 315-094926

TO INITIATING
CIRCUIT OF
SBT, INC.
COMPATIBLE
CONTROL UNIT

DB-11/-11E (NO REMOTE DEVICE)

DB-HR (REMOTE RELAY BASE)

Отзывы: