![Siemens CP 443-5 Extended Скачать руководство пользователя страница 11](http://html.mh-extra.com/html/siemens/cp-443-5-extended/cp-443-5-extended_manual_377095011.webp)
2
Requirements for Use
B4 - 11
CP 443-5 Extended for PROFIBUS / Manual Part B4
Release 6/2005
C79000-G8976-C162-06
2.2
Converting older Systems
The discontinued CPUs listed in Table 2-2 support the following functionality in
conjunction with the CP 443-5 Extended V 6.1:
S
No DPV1 functionality
S
No CiR functionality (DP slave, configurable expansion)
S
No identification of the bus topology by the user program
S
Maximum number of external DP chains per station: 4
S
Number of operable CPs: 8
S
Multicomputing
Table 2-2
Use with no longer available CPU Types - Part 1
CPU
Order number
Version
Number of AG-SEND or AG-RECV
calls at same time
SYNC/FREEZE
CPU 412
6ES7 412-1XF01-0AB0
2 or higher
12 / 12
-
6ES7 412-1XF02-0AB0
2 or higher
12 / 12
+
CPU 413
6ES7 413-1XG01-0AB0
2 or higher
12 / 12
-
6ES7 413-1XG02-0AB0
1 or higher
12 / 12
+
CPU 413-2
6ES7 413-2XG01-0AB0
2 or higher
12 / 12
-
6ES7 413-2XG02-0AB0
1 or higher
12 / 12
+
CPU 414-1
6ES7 414-1XG01-0AB0
2 or higher
12 / 12
-
6ES7 414-1XG02-0AB0
2 or higher
12 / 12
+
CPU 414-2
128 KB
6ES7 414-2XG01-0AB0
2 or higher
12 / 12
-
128 KB
6ES7 414-2XG02-0AB0
2 or higher
12 / 12
+
CPU 414-2
384 KB
6ES7 414-2XJ00-0AB0
4 or higher
12 / 12
-
384 KB
6ES7 414-2XJ01-0AB0
2 or higher
12 / 12
+
CPU 416-1
6ES7 416-1XJ01-0AB0
2 or higher
32 / 32
-
6ES7 416-1XJ02-0AB0
1 or higher
32 / 32
+
CPU 416-2
0 8 MB
6ES7 416-2XK00-0AB0
4 or higher
32 / 32
-
0.8 MB
6ES7 416-2XK01-0AB0
1 or higher
32 / 32
+
CPU 416-2
1.6 MB
6ES7 416-2XL00-0AB0
4 or higher
32 / 32
-
6ES7 416-2XL01-0AB0
1 or higher
32 / 32
+
Legend:
+ => The characteristic is supported / the listed mode is possible
- => The characteristic is not supported / the listed mode is not possible